An exterior masonry chimney is defi ned as a "Masonry" chim-
ney exposed to the outdoors on one or more sides below the
roof line." The ability to use a clay lined masonry chimney
depends on a parameter not associated with interior chimneys.
This variable is the geographic location of the installation.
Researchers have discovered that the winter design tem-
peratures have a direct impact on the suitability of this type
of venting. In most situations, the existing masonry chimneys
will require a properly sized metallic liner.
Throat
Damper
Breech
Clean Out
Typical Multiple Flue Clay Tile Chimney
C
S
HECKLIST
UMMARY
This checklist serves as a summary of the items to be
checked before venting an 80+ furnace into a masonry
chimney. In addition, we recommend that a qualifi ed ser-
viceman use this checklist to perform a yearly inspection of
the furnace venting system.
C
HIMNEYS
O
)
NLY
Wash
Roof Line
Clay Tile Size: 8" x 8" x12"
(Each x 24" Length)
Attic Floor
1/2" to 1" Air Space
Second Floor
First Floor
Water Heater
Vent Connector
F.A.F. Vent
Connector
Natural Draft
Fan Assisted
Water Heater
Forced Air
Furnace
Basement Floor
Figure 3
This checklist is only a summary. For detailed information
on each of the procedures mentioned, see the paragraph
referenced with each item.
Proper Chimney
Termination?
(Check 1)
Chimney channel
free of solid and
liquid fuel
appliances?
(Check 2)
Crown in good
condition
(Check 3)
Cleanout free of
debris?
(Check 4)
Liner in good
condition?
(Check 5)
Dilution air
available?
(Check 6)
Complete the
installation.
(Check 7)
C
1 - P
HECK
ROPER CHIMNEY TERMINATION
A masonry chimney used as a vent for gas fi red equipment
must extend at least three feet above the highest point where it
passes through the roof. It must extend at least two feet higher
than any portion of a building within a horizontal distance of
10 feet. In addition, the chimney must terminate at least 3 feet
above any forced air inlet located within 10 feet. The chimney
must extend at least fi ve feet above the highest connected
equipment draft hood outlet or fl ue collar.
10
Change venting
arrangements
(Fix 2)
Rebuild crown
(Fix 3)
and/or Reline
(Fix 4)
Reline
(Fix 4)
Reline
(Fix 4)
Reline
(Fix 4)
.