Start-Up; General; Crankcase Heaters; Confirm The Input Power Phase Sequence - Carrier Omnizone 50BVC Installation, Start-Up, Service And Controls Operation And Troubleshooting

Water-cooled indoor self-contained systems
Table of Contents

Advertisement

Table 15 — Thermistor Resistance vs Temperature Values for Supply-Air and Return Air Temperature Sensor
TEMP
TEMP
(C)
(F)
-39
-39.44
-37
-38.33
-35
-37.22
-33
-36.11
-31
-35.00
-29
-33.89
-27
-32.78
-25
-31.67
-23
-30.56
-21
-29.44
-19
-28.33
-17
-27.22
-15
-26.11
-13
-25.00
-11
-23.89
-9
-22.78
-7
-21.67
-5
-20.56
-3
-19.44
-1
-18.33
1
-17.22
3
-16.11
5
-15.00
7
-13.89
9
-12.78
11
-11.67
13
-10.56
15
-9.44
17
-8.33
19
-7.22
21
-6.11
23
-5.00
25
-3.89
27
-2.78
29
-1.67
31
-0.56
33
0.56
35
1.67

START-UP

Complete the Start-Up Checklist on page CL-1
General —
before attempting system start-up.
CRANKCASE HEATERS — The 50BVT,V,W,34-064
units include crankcase heaters. Crankcase heaters are ener-
gized as long as there is power to the unit.
Wait 24 hours before starting the compressors to permit
warming by the crankcase heaters.
AFTER 24 hours, continue with the procedures below.
CONFIRM THE INPUT POWER PHASE SEQUENCE —
The input power phase rotation sequence must be L1-L2-L3 =
ABC (or forward or clockwise) as indicated with a phase
rotation meter. Incorrect input phase rotation will cause the com-
pressors to rotate in reverse, which results in no cooling capacity.
IMPORTANT: On VAV units, fan rotation direction
CANNOT be used for the phase sequence check; fan
rotation for VAV units with a variable speed drive is
independent of the unit input wiring sequence.
RESISTANCE
TEMP
(OHMS)
(C)
323,839
37
300,974
39
279,880
41
260,410
43
242,427
45
225,809
47
210,443
49
196,227
51
183,068
53
170,775
55
159,488
57
149,024
59
139,316
61
130,306
63
121,939
65
114,165
67
106,939
69
100,218
71
93,909
73
88,090
75
82,670
77
77,620
79
72,911
81
68,518
83
64,419
85
60,592
87
57,017
89
53,647
91
50,526
93
47,606
95
44,874
97
42,317
99
39,921
101
37,676
103
35,573
105
33,599
107
31,732
109
29,996
111
(10,000 ohms)
TEMP
RESISTANCE
(F)
(OHMS)
2.78
28,365
3.89
26,834
5.00
25,395
6.11
24,042
7.22
22,770
8.33
21,573
9.44
20,446
10.56
19,376
11.67
18,378
12.78
17,437
13.89
16,550
15.00
15,714
16.11
14,925
17.22
14,180
18.33
13,478
19.44
12,814
20.56
12,182
21.67
11,590
22.78
11,030
23.89
10,501
25.00
10,000
26.11
9,526
27.22
9,078
28.33
8,653
29.44
8,251
30.56
7,866
31.67
7,505
32.78
7,163
33.89
6,838
35.00
6,530
36.11
6,238
37.22
5,960
38.33
5,697
39.44
5,447
40.56
5,207
41.67
4,981
42.78
4,766
43.89
4,561
If the compressor is rotating in the wrong direction, it may:
emit increased noise; shut down due to internal overload
protection; have only a small decrease in suction pressure when
it starts; or have only a small increase in discharge pressure
when it starts. Also, no cooling will be produced at the
evaporator. If any of these conditions occurs, refer to the
Service section to correct the compressor rotation before
continuing.
INTERNAL WIRING — Check all electrical connections in
unit control boxes; tighten as required.
RETURN-AIR FILTERS — Check that correct filters are
installed in filter tracks (see Tables 2 and 3). Do not operate
unit without return-air filters.
COMPRESSOR MOUNTING — Compressors are internal-
ly mounted on resilient rubber supports. Do not loosen or re-
move compressor holddown bolts.
REFRIGERANT SERVICE PORTS — Each refrigerant sys-
tem has a total of 2 Schrader-type service gage ports per circuit.
One port is located on the suction line, and one on the compres-
sor discharge line. Be sure that caps on the ports are tight.
24
TEMP
TEMP
RESISTANCE
(C)
(F)
(OHMS)
113
45.00
115
46.11
117
47.22
119
48.33
121
49.44
123
50.56
125
51.67
127
52.78
129
53.89
131
55.00
133
56.11
135
57.22
137
58.33
139
59.44
141
60.56
143
61.67
145
62.78
147
63.89
149
65.00
151
66.11
153
67.22
155
68.33
157
69.44
159
70.56
161
71.67
163
72.78
165
73.89
167
75.00
169
76.11
171
77.22
173
78.33
175
79.44
177
80.56
179
81.67
181
82.78
183
83.89
185
85.00
187
86.11
4,367
4,182
4,006
3,838
3,679
3,525
3,380
3,242
3,111
2,985
2,865
2,751
2,642
2,538
2,438
2,343
2,252
2,165
2,082
2,003
1,927
1,855
1,785
1,718
1,655
1,594
1,536
1,480
1,427
1,375
1,326
1,279
1,234
1,190
1,149
1,109
1,070
1,034