Download Print this page

Tripp Lite SmartOnline SU3000RTXR3U Specifications page 3

3kva on-line double-conversion ups, 3u rack/tower, 110/120v nema outlets, xr runtime
Hide thumbs Also See for SmartOnline SU3000RTXR3U:

Advertisement

Output voltage
+/- 10%
regulation (Economy
line mode)
Output voltage
+/- 2%
regulation (Battery
mode)
Built-in UPS output
4 5-15R outlet(s); 4 5-15/20R outlet(s); 1 L5-30R outlet(s)
receptacles
Built-in controllable
Two switchable four-outlet load banks, (bank 1 - four 5-15/20R, bank 2 - four 5-15R outlets)
switched load banks
Output circuit breaker
15A branch rated (x2) - each breaker protects 4 outlets, L5-30R is unbreakered
Output AC waveform
Sine wave
(AC mode)
Output AC waveform
Pure Sine wave
(battery mode)
INPUT
Rated input current
24A
(at maximum load)
Nominal Input
110V AC; 120V AC
Voltage(s) Supported
UPS input connection
L5-30P
type
Input circuit breaker
40A
UPS Input cord
10
length (ft.)
UPS Input cord
3
length (m)
Recommended
30A 120V
Electrical Service
BATTERY
Full load runtime
12 min. (2400w)
(minutes)
Half load runtime
30 min. (1200w)
(minutes)
Expandable battery
Supports extended runtime with optional external battery packs
runtime
External battery pack
BP72V15-2U
compatibility
DC system voltage
72
(VDC)
Battery recharge rate
Less than 6 hours from 10% to 80%
(included batteries)
Replacement battery
RBC96-3U
cartridge (internal
UPS battery
replacement)
Battery Access
Front panel battery access door
(limit 1);
BP72V28RT-3U
(multi-pack compatible)
(quantity 2)

Advertisement