Verifying Burner Operation; Verifying Operation Of The Supply Air Limit Switch - Nordyne CMF95 Series Installation Instructions Manual

Direct vent (sealed combustion) forced air downflow condensing gas furnace
Hide thumbs Also See for CMF95 Series:
Table of Contents

Advertisement

NOTE: This furnace is designed to operate with a
maximum external pressure rise of 0.3 inches of water
column.It is important that the duct system be designed
to provide the correct flow rates and external pressure
rise. An improperly designed duct system can result
in nuisance shutdowns, and comfort or noise issues.
3. Adjust all registers and duct dampers to the desired
position and run the furnace for 10 to 15 minutes before
taking any temperature readings.The temperature rise
is the difference between the supply and return air
temperatures.

Verifying Burner Operation

CAUTION:
The door over the burners may only be open
for inspection purposes only.The door must be
installed during unattended operation.
1. Set the thermostat above room temperature and observe
the ignition sequence. NOTE: The burner flame should
carry over immediately between all burners without
lifting off, curling, or floating.The flames should be blue,
without yellow tips.
2. After validating the flame, change thermostat setting to
below room temperature.
3. Verify the burner flame is completely extinguished.
MODEL NUMBER
& HEATING INPUT
(BTUH)
CMF95 045
45,000
CMF95 072
72,000
NOTES:
* Factory Set Cooling Speed.
** Factory Set Heating Speed.
1. Temperature rises (° F) in the table are approximate. Actual temperature rises may vary.
2. Temperature rises shaded in gray are for reference only. These conditions are not recommended.
3. Airflow performance is with a filter.
24
EXTERNAL STATIC PRESSURE (INCHES WATER COLUMN)
MOTOR
0.1
SPEED
CFM
RISE
HIGH*
1380
29
MED HIGH
1350
29
MED LOW
1100
36
LOW**
1000
40
HIGH*
1485
43
MED HIGH**
1263
50
MED LOW
1130
56
LOW
880
72
Table 5. Maximum Airflow & Temperature Rises (° F)
4. Replace the burner compartment door.
Verifying Operation of the Supply Air Limit
Switch
Note: A properly functioning limit switch should turn off
the gas valve when the return is blocked (time depends
on how well the return air is blocked). The circulating air
and combustion blowers should continue to run when the
limit switch opens.
1. Verify the blower door is securely mounted in place and
that there is power to the furnace.
2. Block the return airflow to the furnace by installing a
close-off plate in place of or upstream of the filter(s).
3. Set the thermostat above room temperature and observe
the Operating Sequence.
4. Remove the close-off immediately after the limit switch
opens.If the furnace continues to operate with no return
air, set the thermostat below room temperature, shut
off power to the furnace, and replace the limit switch.
0.2
0.3
CFM
RISE
CFM
RISE
1335
30
1290
31
1295
31
1240
32
1055
38
1020
39
970
41
935
42
1440
44
1390
46
1235
51
1205
53
1100
58
1175
54
846
75
830
76
0.4
0.5
CFM
RISE
CFM
RISE
1230
32
1175
34
1190
33
1135
35
975
41
920
43
900
44
860
46
1340
47
1290
49
1160
55
1115
57
1045
61
1000
63
805
79
770
82