Honeywell Farenhyt Series Installation And Operation Manual page 122

Addressable fire alarm control system emergency communication system
Hide thumbs Also See for Farenhyt Series:
Table of Contents

Advertisement

3.
Press 4 to enter point menu.
4.
Press the up or down arrow key to select the desired module. Refer to Section 8.5 Quick Reference Table for available choices.
Then press ENTER.
5.
Select S for sensor or M for module. (IDP or SK Only)
6.
Enter the number of the point you wish to edit, then press ENTER.
7.
Select the type of device by pressing the up or down arrow key. Refer to Table 9.5 under the column heading "Type Selection" for a
list of choices.
Type Selection
UNUSED
DETECTOR
SUP DET
CO SMOKE
DETECTOR
W-DETECTOR
W-SUP DET
IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017
Function
Latching Option
PHOTO
ION
HEAT
PHOTO DUCT
ACCLIMATE
HEAT HT
PHOTO-HEAT
BEAM
2-WIRE SMOKE
PHOTO
Latching
Non Latching
ION
HEAT
PHOTO DUCT
ACCLIMATE
HEAT HT
PHOTO-HEAT
BEAM
CO ALRM /
FIRE ALRM
CO ALRM /
FIRE SUPR
CO SUPR /
FIRE ALRM
CO SUPR /
Latching
FIRE SUPR
Non Latching
PHOTO
Latching
Non Latching
ACCLIMATE (IDP)
PHOTO-HEAT (SK)
HEAT
Same as W-
Latching
Detector
Non Latching
Table 9.5 Programming Options for 6815 Modules
Comments
Select for SLC points that are unused.
Spot photoelectric detectors.
Spot ionization detector.
Spot heat detector.
Duct photoelectric detector.
Acclimate photoelectric detector.
High temperature heat detector.
Photoelectric detector with heat sensor.
Beam smoke detector.
2-wire smoke detector.
Use this option when you want a detector to indicate a supervisory
alarm.
Supervisory switches can be latching or non-latching.
Wireless photoelectric detectors.
Wireless acclimate photoelectric detector.
Wireless heat detector.
Wireless photoelectric detectors.
118