Weil-McLain CGA Series 2 Manual page 65

Gas-fired water boilers
Hide thumbs Also See for CGA Series 2:
Table of Contents

Advertisement

CGa Series 2 Gas-Fired Water Boiler — Boiler Manual
13b
Ratings
Boiler
model
0 - 2,000 feet
number
Altitude
Input
(Note 1)
(Btuh)
52,000
CGa-25
70,000
CGa-3
105,000
CGa-4
140,000
CGa-5
175,000
CGa-6
210,000
CGa-7
245,000
CGa-8
1. Add "PIN" for natural gas boiler - "PIL" for Liquefied Petroleum (propane) gas boiler.
2. Based on standard test procedures prescribed by the United States Department of Energy.
Notes
3. Net AHRI ratings are based on net installed radiation of sufficient quantity for the requirements of the
building and nothing need be added for normal piping and pickup. Ratings are based on a piping and pickup
allowance of 1.15. An additional allowance should be made for unusual piping and pickup loads.
Table 8 Ignition system model suffixes
Install CGa boilers for residential radiant panel systems, converted gravity heating systems or other low water
temperature applications per instructions in this manual to avoid damage due to condensation.
CGa boilers are CSA design certified for installation on combustible flooring.
CGa boilers are ASME rated for 50 psig working pressure.
Part Number 550-142-900/0519
2,000 - 4,500 feet
Altitude
Output
Input
Output
(Btuh)
(Btuh)
(Btuh)
44,000
46,800
39,000
59,000
63,000
53,000
88,000
94,500
79,000
117,000
126,000
105,000
146,000
157,500
131,000
175,000
189,000
157,000
204,000
220,500
183,000
AHRI Certiified Ratings
Seasonal
Efficiency
Heating
Capacity
PIDN-PIDL
Btuh
AFUE
%
(Note 2)
44,000
84.0
59,000
84.0
88,000
84.0
117,000
83.5
146,000
83.2
175,000
83.0
204,000
82.7
Pilot ignition system
Spark-ignite pilot
Chimney
Boiler
water
breeching
Net
content
Ratings
Btuh
(gallons)
Inches
(Note 3)
38,000
1.5
4"I.D. x 20'
51,000
1.5
4"I.D. x 20'
77,000
2.1
5"I.D. x 20'
102,000
2.7
6"I.D. x 20'
127,000
3.3
6"I.D. x 20'
152,000
3.8
7"I.D. x 20'
177,000
4.4
7"I.D. x 20'
Natural gas
Propane gas
PIDN
PIDL
and
size
65

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cga-25Cga-3 cga-4Cga-5Cga-6Cga-7Cga-8

Table of Contents