SETUP
OUTPUTS
RELAY 1

RESET RT

Fig. 78. Setup - Outputs - Relay - Reset Runtime.
4. SCHEDULING
Scheduling provides the ability to set daily temperature
settings for up to two events per day. Typically, these are
the daytime (setpoint) and the nighttime (setback)
settings.
IMPORTANT
To enable Scheduling, you must first enter Setup
mode (press and hold the MENU button for 5
seconds), select OUTPUTS, select OPTIONS,
select USE SCHED, and then select YES. (Refer
to "3.3.5.1. USE SCHED" on page 26).
IMPORTANT
To properly account for Daylight Saving time, be
sure to set the Date before setting the Time.
Refer to "4.2.2. SET DATE" on page 33.
NOTE: The T775R controller interface is intuitive.
You may find that you do not need the follow-
ing scheduling instructions. You may want to
use this procedure simply as a reference to
locate the particular option or parameter of
interest.
T775R SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
SETUP
OUTPUTS
RELAY 1
RESET RT
YES
NO
RESET
RUN TIME
FOR
RELAY 1
M24357
31
3.3.6.4. RESET RT
This selection displays only if "Show RT = YES" is
selected during Output Options setup (Refer to "3.3.5.4.
SHOW RT (show run time hours)" on page 27).
1. Press the  button to display the Reset RT values.
2. Use the  and  buttons to select YES or NO.
Default: NO
3. Press the  button to accept the value and return to
the Relay menu.
Selecting YES immediately resets the output run time
hours to zero for this output. When you subsequently
return to this screen, the RESET RT defaults to NO.
NOTE: Run times can be reset to zero for each
individual relay. You must do this for each
relay that you want to reset to zero.

3.3.7. Setup the Next Relay

To setup the next relay output go to "3.3.6. Setting up the
Relays" on page 28.

3.4. Exiting Setup

Press the  button to exit the selected relay set up and
return to the Outputs menu.
If you are finished setting up the relay outputs, press the
HOME button to exit Setup mode and return to the home
screen display.
This completes the Setup procedure.
NOTE: Each output is independently configurable to
follow the schedule or not. For modulating
outputs, Refer to "3.3.3.1.5. SCHEDULE" on
page 24. For relay outputs, Refer to "3.3.6.2.
SCHEDULE" on page 30.
NOTES:
If you press the HOME button or there is no
1.
keypad activity for four minutes, you exit
Scheduling mode and return to the home
screen.
If you press the MENU button, you exit
2.
Scheduling mode and return to the menu.
To create or change a schedule, you use the —
• Left arrow button () to scroll backward through the
Schedule menus
• Right arrow button () to select the highlighted menu
item and display its content
• Up and Down arrow buttons ( and ) to scroll up
and down through a list of items or to increase or
decrease the value of a displayed schedule parameter
(run time)
62-0249—13