Download Print this page

Elta Quietflow SQS Series Installation And Maintenance Instructions

Advertisement

Quick Links

Quietflow SQS
Installation and Maintenance Instructions
THESE INSTRUCTIONS MUST BE READ FULLY BEFORE
COMMENCING INSTALLATION
Code
SQS125-L
SQS150-L
SQS200-L
SQS250-L
SQS315-11L
SQS315-L
SQS315-33L
SQS400-L
SQS500-L
Code
A
SQS125-L
400
SQS150-L
425
SQS200-L
425
SQS250-L
475
SQS315-11L
575
SQS315-L
575
SQS315-33L
650
SQS400-L
700
SQS500-L
850
Supply
230V/1Ph/50Hz
230V/1Ph/50Hz
230V/1Ph/50Hz
230V/1Ph/50Hz
230V/1Ph/50Hz
230V/1Ph/50Hz
230V/1Ph/50Hz
230V/1Ph/50Hz
230V/1Ph/50Hz
B
C
375
210
500
260
500
260
550
300
700
440
700
440
700
440
800
460
900
570
FL Amps
Output kW
0.47
0.100
0.82
0.165
0.82
0.185
0.95
0.220
1.20
0.250
3.10
0.650
3.70
0.840
6.50
1.400
8.50
1.500
D
F
125
200
150
225
200
225
250
275
315
375
315
375
315
375
400
500
500
650
r/min
1700
1750
1500
1520
1220
1350
1300
1220
750
G
Weight kg
425
12
550
16
550
17
600
19
750
34
750
34
750
34
850
46
950
58

Advertisement

loading

Summary of Contents for Elta Quietflow SQS Series

  • Page 1 Quietflow SQS Installation and Maintenance Instructions THESE INSTRUCTIONS MUST BE READ FULLY BEFORE COMMENCING INSTALLATION Code Supply FL Amps Output kW r/min SQS125-L 230V/1Ph/50Hz 0.47 0.100 1700 SQS150-L 230V/1Ph/50Hz 0.82 0.165 1750 SQS200-L 230V/1Ph/50Hz 0.82 0.185 1500 SQS250-L 230V/1Ph/50Hz 0.95 0.220 1520 SQS315-11L...
  • Page 2 Upon receipt, the fan equipment should be visually inspected to check for any damage. Ensure that the impeller is free to rotate. If there are any queries concerning the fan equipment, Elta Fans Ltd should be contacted prior to the installation.
  • Page 3 START-UP Before power is supplied to the unit, check that the wiring is correct as per the fan connection diagram. At initial start-up, check that impeller rotation and airflow direction is correct. Check that the motor amperage draw does not exceed the nameplate rating. FAN MAINTENANCE Inspection of the fan at least once every 12 months is recommended to ensure that the motor, fan blades, and supporting guards, are clean.
  • Page 4 GUARANTEE Elta Fans Ltd will, free of charge, within a period of 1 year from the date of despatch from their works, repair or at its option replace any goods which are proved to have defects as a result of defective materials or workmanship.

This manual is also suitable for:

Quietflow sqs125-lQuietflow sqs150-lQuietflow sqs200-lQuietflow sqs250-lQuietflow sqs315-11lQuietflow sqs315-l ... Show all