(Capacity Loading Sequence) - Carrier ComfortLink 6 Series Controls, Start-Up, Operation, Service, And Troubleshooting

Air-cooled and water-cooled chillers with controls 50/60 hz
Hide thumbs Also See for ComfortLink 6 Series:
Table of Contents

Advertisement

Capacity Loading Sequence Example —
lowing tables show the loading sequence for a 30HX186
(50/50 split) and a 30HX161 (59/41 split) chiller. Each
STANDARD LOADING SEQUENCE (CIRCUIT A LEAD CIRCUIT, 2-COMPRESSOR UNIT)
COMP
LOADER
STAGE
A1
0
0
1
1
2
1
3
1
4
1
5
1
6
1
CLOSE CONTROL LOADING SEQUENCE (CIRCUIT A LEAD CIRCUIT, 2-COMPRESSOR UNIT)
COMP
LOADER
STAGE
A1
0
0
1
1
2
1
3
1
3A
1
3B
1
4
1
5
1
6
1
LEGEND
0 — Off
1 — On
NOTES:
1. Stage 3A (and 3B for 59/41 split) is not used by the algorithm
when increasing stages. Stage 3 (and 2 for a 59/41 split) is not
used when decreasing stages.
2. The % Total Capacities above are calculated based on compres-
sor nominal tons. For the case of the 59/41 split above, the 30HX
uses compressors with flow rates of 250 and 174 cfm (from com-
pressor model numbers 06N__250 and 06N__174), which repre-
sent nominal tons of 80 and 56 (respectively) at 60 Hz. A factor of
40% is used when no loaders are energized, and a factor of 70%
is used when Loader 1 is energized. The capacity shown for
Stage 3B above is calculated as follows:
% Total Capacity = [(0.40 x 80 + 0.70 x 56)/(80 + 56)] x 100%
= 52.4 %
The fol-
LOADER
COMP
A1
A2
B1
0
0
0
0
0
0
1
0
0
1
1
0
1
0
1
1
0
1
1
1
1
LOADER
COMP
A1
A2
B1
0
0
0
0
0
0
1
0
0
1
1
0
0
0
1
0
0
1
0
0
1
1
0
1
1
1
1
APPENDIX B
compressor has 2 loaders. There is no difference in operation
between "Staged" and "Equal" circuit loading on 2 compressor
chillers.
LOADER
LOADER
B1
B2
0
0
0
0
0
0
0
0
1
0
1
1
1
1
LOADER
LOADER
B1
B2
0
0
0
0
0
0
0
0
0
0
1
0
1
1
1
1
1
1
COMPRESSOR
PART NO.
06N__123
06N__146
06N__174
06N__209
06N__250
06N__300
85
% TOTAL
% TOTAL
CAPACITY
CAPACITY
(50/50 Split)
(59/41 Split)
0.0
20.0
23.5
35.0
41.1
50.0
58.8
70.0
70.0
85.0
82.4
100.0
100.0
% TOTAL
% TOTAL
CAPACITY
CAPACITY
(50/50 Split)
(59/41 Split)
0.0
20.0
23.5
35.0
41.1
50.0
58.8
40.0
40.0
55.0
52.4
70.0
64.7
85.0
82.4
100.0
100.0
Nominal Tons
60 Hz NOM.
50 Hz NOM.
TONS
TONS
39
46
56
66
80
0.0
0.0
39
46
56
66
80