Configuring
Exit to pro-
9
Press button
cess control
level
10
Press button
Controller is now in manual mode.
+
NOTE
[ ] reflects the factory setting.
Configuring switch list
Config.
Setting
switch
S1
Controller type
[0]
Fixed setpoint / three-component controller/controller with 2 internal set-
points
1
Fixed setpoint / three-component controller with 5 internal setpoints
2
Slave/synchro/SPC controller with internal/external switchover
3
Ratio controller
4
Control station / process variable indicator
5
Program controller (not for types 6DR1901-, 6DR1904-)
6
Fixed setpoint controller with one setpoint
7
Slave controller without int/ext switchover
1)
as of software version 3
S2
Output structure
[0]
K-output
1
S-output:
2
S-output:
3
S-output:
S3
Mains frequency suppression
[0]
50 Hz
1
60 Hz
S4
Standard input AI1 (I, mV, R, P, T) - Transmitter fault signal
[0]
UNI-input
1
UNI-input
2
UNI-input
3
UNI-input
S5
Input signal AI1
[0]
mV (linear), with range plug I [mA] or U [V]
1
Thermocouple with internal reference junction
2
Thermocouple with external reference junction
60
(13) once (selection level).
(13) once (process control level).
Function
1)
1)
Two-step controller with 2 outputs heating/cooling
Three-step controller for motorized drives, internal
feedback
Three-step controller for motorized drives,
external feedback
AI1
min
on sensor breakage
AI1
min
on sensor breakage
AI1
max
on sensor breakage
AI1
max
on sensor breakage
Quick Reference
without MUF
with MUF
without MUF
with MUF
SIPART DR19