Cisco Catalyst 9500 Series Hardware Installation Manual page 64

Hide thumbs Also See for Catalyst 9500 Series:
Table of Contents

Advertisement

Connecting to a DC Power Source
3. Secure the positive (+) DC power cable lug to the RTN terminal and the negative (–) DC power cable
4. Replace the safety cover over the terminal box on the DC power supply.
Step 5
Verify that the power supply is receiving power by checking that the LED is on and is amber or red. For more
information about the power supply LEDs and the conditions that they indicate, see
When you first activate the power supply, you can verify the functionality of the LED by checking that LED
turns on for a couple of seconds. If the LED is flashing amber or red, check the power connections on the
power supply and the power source.
Cisco Catalyst 9500 Series Switches Hardware Installation Guide
56
Figure 39: Removing the Nuts on the Terminal Box
lug to the –48V terminal with the nuts.
To tighten the nuts, apply torque between 7 lbf.in (0.8Nm) and 10lbf.in (1.1 Nm) to each nut.
Installing Field Replaceable Units
Power Supply
LEDs.