Carrier Weathermaster 48P2030-100 Controls, Start-Up, Operation, Service, And Troubleshooting page 248

Single package large rooftop units with comfortlink version 7.x controls
Table of Contents

Advertisement

ITEM
BP
BP.CF
BP.S
BP.R
BP.SP
BP.SO
BP.P1
BP.P2
B.V.A
B.V.ABP.FS
B.V.ABP.MN
B.V.ABP.MX
B.V.ABP.1M
B.V.ABP.2M
B.V.ABP.CL
FAN.T
FAN.TFT.CF
FAN.TFT.TM
FAN.TFT.ST
FAN.TFT.MX
FAN.TFT.AD
FAN.TFT.OF
FAN.TFT.RM
FAN.TFT.RS
FAN.TSCF.C
B.PID
B.PIDBP.TM
B.PIDBP.P
B.PIDBP.I
B.PIDBP.D
ACT.C
ACT.CBP.1
ACT.CBP.1SN.1
ACT.CBP.1SN.2
ACT.CBP.1SN.3
ACT.CBP.1SN.4
ACT.CBP.1C.A.LM
ACT.CBP.2
ACT.CBP.2SN.1
ACT.CBP.2SN.2
ACT.CBP.2SN.3
ACT.CBP.2SN.4
ACT.CBP.2C.A.LM
D.LV.T
L.H.ON
H.H.ON
L.H.OF
L.C.ON
H.C.ON
L.C.OF
C.T.LV
H.T.LV
C.T.TM
H.T.TM
DMD.L
DM.L.S
D.L.20
SH.NM
SH.DL
SH.TM
D.L.S1
D.L.S2
CONTROLS SET POINT AND CONFIGURATION LOG (cont)
EXPANSION
BUILDING PRESS. CONFIGS
Building Press. Config
Building Pressure Sensor
Bldg. Press. (+/-) Range
Building Pressure Setp.
BP Setpoint Offset
Power Exhaust On Setp.1
Power Exhaust On Setp.2
VFD/ACTUATOR CONFIG
VFD/Act. Fire Speed/Pos.
VFD/Act. Min.Speed/Pos.
VFD Maximum Speed
BP 1 Actuator Max Pos.
BP 2 Actuator Max Pos.
BP Hi Cap VFD Clamp Val.
FAN TRACKING CONFIG
Fan Track Learn Enable
Fan Track Learn Rate
Fan Track Initial DCFM
Fan Track Max Clamp
Fan Track Max Correction
Fan Track Internl EEPROM
Fan Track Internal RAM
Fan Track Reset Internal
Supply Air CFM Config
BLDG.PRESS.PID CONFIGS
Bldg.Pres.PID Run Rate
Bldg.Press. Prop. Gain
Bldg.Press. Integ. Gain
Bldg.Press. Deriv. Gain
BLDG.PRES. ACTUATOR CFGS
BLDG.PRES. ACT.1 CONFIGS
BP 1 Serial Number 1
BP 1 Serial Number 2
BP 1 Serial Number 3
BP 1 Serial Number 4
BP1 Cntrl Angle Lo Limit
BLDG.PRES. ACT.2 CONFIGS
BP 2 Serial Number 1
BP 2 Serial Number 2
BP 2 Serial Number 3
BP 2 Serial Number 4
BP2 Cntrl Angle Lo Limit
COOL/HEAT SETPT. OFFSETS
Dmd Level
Lo Heat On
Dmd Level(+) Hi Heat On
Dmd Level(-) Lo Heat Off
Dmd Level
Lo Cool On
Dmd Level(+) Hi Cool On
Dmd Level(-) Lo Cool Off
Cool Trend Demand Level
Heat Trend Demand Level
Cool Trend Time
Heat Trend Time
DEMAND LIMIT CONFIG.
Demand Limit Select
Demand Limit at 20 ma
Loadshed Group Number
Loadshed Demand Delta
Maximum Loadshed Time
Demand Limit Sw.1 Setpt.
Demand Limit Sw.2 Setpt.
RANGE
0 to 5 (multi-text strings)
Enable/Disable
0.10 to 0.25 " H2O
-0.25 to 0.25 " H2O
0 to 0.5 " H2O
0 to 100%
0 to 100%
0 to 100%
0 to 50%
50 to 100%
85 to 100%
85 to 100%
5 to 25%
Yes/No
5-60 min
-20000 to 20000 CFM
0 to 20000 CFM
0 -20000 CFM
-20000 to 20000 CFM
-20000 to 20000 CFM
Yes/No
1 to 2 (multi-text strings)
5 to 120 sec
0 to 5
0 to 2
0 to 5
0 to 9999
0 to 6
0 to 9999
0 to 254
0-90
0 to 9999
0 to 6
0 to 9999
0 to 254
0-90
–1 to 2 ^F
0.5 to 20.0 ^F
0.5 to 2.0 ^F
–1 to 2 ^F
0.5 to 20.0 ^F
0.5 to 2.0 ^F
0.1 to 5.0 ^F
0.1 to 5.0 ^F
30 to 600 sec
30 to 600 sec
0 to 3 (multi-text strings)
0 to 100%
0 to 99
0 to 60%
0 to 120 min
0 to 100%
0 to 100%
CL-4
DEFAULT
SETTING
0
Disable
0.25
0.05
0.05
25
75
100
0
100
100
100
10
No
15
2000
4000
1000
0
0
No
1
10
0.5
0.5
0.3
0
0
0
0
35
0
0
0
0
35
1.5
0.5
1.0
1.5
0.5
1.0
0.1
0.1
120
120
0
100
0
0
60
80
50

Hide quick links: