York MILLENIUM SIMPLICITY ELITE Series Technical Application And Programming Manual page 17

Single package rooftop units 25, 30 & 40 ton equipped with controls
Table of Contents

Advertisement

Table 5: Settable System Parameters (Continued)
Address
Exhaust Damper Position for Exhaust Fan to
47
Turn Off (Modulating Only)
Economizer Damper Position for Exhaust Fan
48
to Turn On (Non-Modulating Only)
Economizer Damper Position for Exhaust Fan
49
to Turn Off (Non-Modulating Only)
50
51
Dirty Filter Switch
52
Dirty Filter Switch Data
53
Cooling Mode Enable
54
Heating Mode Enable
55
Fan On Mode with the Sensor Option
56
Space Setpoint Offset
57
Metric Operation
58
BAS Economizer
59
60
61
62
63
64
65
SAT (Supply Air Temp)
66
RAT (Return Air Temp)
67
OAT (Outside Air Temp)
68
ST (Space Temp)
69
OAH (Outside Air Hum)
70
RAH (Return Air Hum)
71
Occupied Input Enable
72
73
74
75
76
77
78
Hot Gas Reheat
79
Hot Gas Bypass
80
81
82
Duct Static Reading
83
Building Pressure Reading
84
Low Ambient Kit Installed
85
Building Static Pressure Sensor Enable
86
87
ERV Unoccupied Fan
88
Duct Static Shutdown Setpoint
NOTES:
For On/Off functions, 1 is ON and 0 is OFF
Read only items are readings from sensors which only change as the measured condition changes.
Johnson Controls Unitary Products
Function
APS Data
Year
Month
Day of Month
Day of Week
Hour
Minute
Alarm Array
Alarm Array
These values represent the last 5 alarm codes in
Alarm Array
Alarm Array
Alarm Array
CV/VAV Mode
Compressors
Heat Stages
ERV Installed
Unit
% Of Damper Position
% Of Damper Position
Percent of Economizer
0-100%
Position
Open-Closed
Open-Closed
ON-OFF
ON-OFF
Open-Closed
Open-Closed
ON-OFF
ON-OFF
ON-OFF
ON-OFF
ON-OFF
ON-OFF
°F
ON-OFF
ON-OFF
ON-OFF
ON-OFF
Year
Month
Number
Day
Number
Day
Number
Hour
Minutes
°F
-40 to 180
°F
-40 to 180
°F
-40 to 180
°F
-40 to 180
%RH
0 to 100%
%RH
0 to 100%
ON-OFF
ON-OFF
memory. 72 is latest & 76 oldest.
Read Only Flag
CV=0
ON-OFF
ON-OFF
ON-OFF
ON-OFF
Number
Number
Inches Water
0 to 5.0"
Inches Water
0 to 5.0"
ON-OFF
ON-OFF
ON-OFF
ON-OFF
ON-OFF
ON-OFF
ON-OFF
ON-OFF
Inches Water
0 to 5.0"
Range
Default
0-100
20%
0-100
60%
20%
Open
OFF
Open
ON
ON
ON
-5 to 5
0 degrees
OFF
OFF
00-99
4
1
1
1
0-23
0
0-59
0
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
OFF
Read Only
Read Only
Read Only
Read Only
Read Only
VAV=1
Read Only
OFF
OFF
2 to 4
Factory Set
0 to 3
Factory Set
Read Only
Read Only
Factory Set
Factory Set
Factory Set
Factory Set
4.5"
351579-YTS-B-0608
Your Settings
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
17