Settable System Parameters - York MILLENIUM SIMPLICITY ELITE Series Technical Application And Programming Manual

Single package rooftop units 25, 30 & 40 ton equipped with controls
Table of Contents

Advertisement

351579-YTS-B-0608
Table 5: Settable System Parameters
Address
1
2
Fan on delay-Heating
3
Fan off delay-Heating
4
Fan on delay-Cooling
5
Fan off delay-Cooling
6
7
Suspend Cont Fan when starting Heating
8
Construction Mode
9
Unoccupied Override Time Period
10
Occupied Cooling Setpoint
11
Occupied Heating Setpoint
12
Unoccupied Cooling Setpoint
13
Unoccupied Heating Setpoint
14
SAT Control-Cooling
15
Cooling SAT Control Setpoint
16
SAT Control for Heating
17
Heating SAT Control Setpoint
18
Hydronic Heating
19
First Stage Hydronic Heating SAT Setpoint
20
Second Stage Hydronic Heating SAT Setpoint
21
Hydronic Heating Reverse Actuated Valve
22
Remote Control
23
VAV Upper Cooling SAT
24
VAV Lower Cooling SAT
25
VAV SAT Reset Setpoint
26
VAV Occupied Setpoint
27
VAV Occupied Heating Setpoint
28
Morning Warm-Up
29
Morning Warm-Up RAT
30
Duct Static Setpoint
31
Building Pressure Setpoint
32
33
Economizer First Stage
34
Economizer Second Stage
35
Economizer Minimum Position
36
Outside Air Humidity Sensor
37
Economizer Outside Air Enthalpy Setpoint
38
Return Air Humidity Sensor
39
Economizer OAT Enable
40
Demand Ventilation
41
IAQ Sensor Range
42
Demand Ventilation Setpoint
43
44
Modulating Exhaust
45
Exhaust VFD Installed
Exhaust Damper Position for Exhaust Fan to
46
Turn On (Modulating Only)
16
Function
Run test
Factory setting
Economizer
Power Exhaust
Unit
Range
ON-OFF
Sec
Sec
Sec
Sec
-
ON-OFF
-
ON-OFF
Minutes
°F
°F
°F
°F
ON-OFF
ON-OFF
°F
ON-OFF
ON-OFF
°F
100-180
ON-OFF
ON-OFF
°F
80-180
°F
80-180
ON-OFF
ON-OFF
ON-OFF
ON-OFF
°F
°F
°F
ON-OFF
ON-OFF
°F
ON-OFF
ON-OFF
°F
" H2O
" H2O
neg .25 to .25
ON-OFF
ON-OFF
°F
°F
Percent
0 to 100%
ON-OFF
ON-OFF
BTUs Per Pound
ON-OFF
ON-OFF
°F
ON-OFF
ON-OFF
PPM
0-5000
PPM
0-5000
ON-OFF
ON-OFF
ON-OFF
ON-OFF
ON-OFF
ON-OFF
% Of Damper Position
Default
OFF
0-30
30
0-255
60
0-30
0
0-255
30
-
1
OFF
OFF
0-240
60
45-99
72
45-99
68
45-99
85
45-99
60
ON
40-65
50
ON
135
OFF
120
150
OFF
OFF
40-70
60
40-70
55
40-85
72
OFF
40-85
68
ON
50-85
70
0 – 5"
1.5"
.1"
ON
40-65
55
40-65
50
20
OFF
10-50
27
OFF
40-80
55
OFF
2000
1000
ON
OFF
OFF
0-100
80%
Johnson Controls Unitary Products
Your Settings