Safety Check-off List
Recommendations
Follow installation manual instructions.
Verify incoming gas pressure.
Verify the BTU rating of gas meter.
Verify that the pipe size meets the input BTU rating of the appliance
Verify combustion air supply meets code requirements (consult local authorities for prevailing codes).
Verify that area around appliance is free of lint or pet hair.
Verify condition and size of chimney and venting. Venting must comply with code, including construction, size
and liner requirements.
Verify condition and routing of flue pipe. Total length should be as short as possible (note the quantity of elbows,
tees, and location of draft regulators).
Verify type of draft regulator.
Verify clearances to combustibles, including chimney connector, burner, and appliance.
NOTICE: A manometer and combustion analyzer are required tools for proper installation and adjustment.
When Converting from Oil to Gas
Thoroughly clean heat exchanger of appliance.
Replace chamber kit.
Seal up boiler sections, clean out plates and boiler mounting plate.
Install double action draft regulator.
Install thermal safety switch (ex. Field Controls GSK-3 or similar).
Adjust burner to operate at no less than 90% of input of the appliance rating plate (GPH x 140,000 x .9 = lowest
BTU firing rate).
Verify stack temperature is at a minimum of 325°F or appliance manufacturer's recommended setting.
Be aware that failure to maintain proper stack temperature could result in condensed flue gas and cause chimney
damage which could result in CO leakage into dwelling.
How To order a Complete Burner from the chart below :
1). Select the Burner Chassis Part Number.
2). Air Tube Combination Part Number.
3). Assemble following the manual supplied with the burner
chassis.