CM582-DP
Certification
13.4.1
Interface for PROFIBUS
Pin Assignment
13.5
Cleaning
13.6
Certification
110
Pin
Signal
1
NC
2
NC
3
RxD/TxD-P
4
CNTR-P
5
DGND
6
VP
7
NC
8
RxD/TxD-N
9
NC
In corrosive environment, please protect unused connectors using the TA535
accessory.
Not supplied with this device.
Cleaning instruction
Do not use cleaning agent for cleaning the device.
Use a damp cloth instead.
3ADR024117M02xx, 11, en_US
Description
Not connected
Not connected
Receive/Transmit positive
Control signal for repeater, positive
Reference potential for data exchange
and +5 V
+5 V (power supply for the bus termi-
nating resistors)
Not connected
Receive/Transmit negative
Not connected