UNIT INsTallaTIoN aNd
servIce MaNUal
FG-A1
12 Volt Battery Back-Up
Power Supply
NOTE! TO ThE iNSTAllEr: Please make sure
you provide this manual to the owner of the
pumping equipment or to the responsible party
who maintains the system.
293 WriGhT STreeT, Delavan, Wi 53115 WWW.hyDrOmaTic.cOm
Ph: 888-957-8677
269 Trillium Drive, KiTchener, OnTariO, canaDa n2G 4W5
Ph: 519-896-2163
W-03-435 (rev. 03/04/13)
© 2013 Pentair, ltd. all rights reserved.

Advertisement

loading

Summary of Contents for Pentair HYDROMATIC FG-A1

  • Page 1 293 WriGhT STreeT, Delavan, Wi 53115 WWW.hyDrOmaTic.cOm Ph: 888-957-8677 269 Trillium Drive, KiTchener, OnTariO, canaDa n2G 4W5 Ph: 519-896-2163 W-03-435 (rev. 03/04/13) © 2013 Pentair, ltd. all rights reserved.
  • Page 2: General Information

    • Group 24 batteries will fit General FG-A1 and into the battery box with Information Pump Warning maximum battery dimensions of 12" long x 6­1/2" wide x 9" high to the top of the CAUTION AND WARNING Before Operation: terminals. Read following in struc­...
  • Page 3: Installation

    come on and the buzzer sounds for the ALARM function. Battery FG-A1 should be checked by a battery shop. Installation 5. Assemble back­up pump a minimum of 1" above the primary pump and tilt 30° (per Figure 1 below). The enclosed pump includes a built­in check valve and screws 1.
  • Page 4 FG-A1 Installation 8. Insert the plug of the pump into the PUMP socket of the control panel. 9. Push the RESET button and the unit is ready for operation. 10. The back­up sump pump should be checked by unplugging the primary sump pump and filling the sump basin with water.
  • Page 5 buzzer will sound. When the The CHARGED in di ca tor will be FG-A1 Testing FLOAT switch turns the backup ON until the DC voltage drops. and Operation OFF, the buzzer will con tin ue to The battery will start charging sound until the ALARM switch is again CHARG ING...
  • Page 6: Backup System

    LED’s will alternate between will be necessary to remove the Q & A FG-A1 “CHARGED” & “CHARGING.” battery and have it charged on a commercial automotive or Backup System Q. Finally, LED’s quit marine battery charger, per the alternating manufacturer’s instructions.
  • Page 7: Parts List

    Q & A FG-A1 Back-Up System Q. Why is it necessary to install the pump at an angle? A. Installing the pump at an angle prevents air from entering the system. If air were allowed to enter the system, the pump would not operate. Q.
  • Page 8 Limited Warranty HYDROMATIC warrants to the original consumer purchaser (“Purchaser” or “You”) of HYDROMATIC Sump Pumps, Effluent Pumps, Sewage Pumps (other than 2-1/2”), and Package Systems, that they will be free from defects in material and workmanship for the Warranty Period of 36 months from date of manufacture. Our warranty will not apply to any product that, in our sole judgement, has been subject to negligence, misapplication, improper installation, or improper maintenance.