Samsung AR TXHZ Series Installation Manual page 6

Hide thumbs Also See for AR TXHZ Series:
Table of Contents

Advertisement

Safety Information
Make sure that the labels are affixed on the system to
notify it contains flammable refrigerant.
Recovery
When removing refrigerant from the system for
servicing or decommissioning, it is recommended to
remove the entire refrigerant.
When transferring refrigerant into cylinders, make sure
that only the refrigerant recovery cylinders are used.
All cylinders used for the recovered refrigerant shall
be labelled.
Cylinders shall be equipped with pressure relief valves
and shut-off valves in a proper order.
Empty recovery cylinders shall be evacuated and
cooled before recovery.
The recovery system shall operate normally according
to the specified instructions and shall be suitable for
refrigerant recovery.
In addition, the calibration scales shall operate
normally.
Hoses shall be equipped with leak-free disconnect
couplings.
Before starting the recovery, check for the status of the
recovery system and sealing state. Consult with the
manufacturer if suspected.
The recovered refrigerant shall be returned to the
supplier in the correct recovery cylinders with the
Waste Transfer Note attached.
Do not mix refrigerants in the recovery units or
cylinders.
If compressors or compressor oils are to be removed,
make sure that they have been evacuated to the
acceptable level to ensure that flammable refrigerant
does not remain in the lubricant.
The evacuation process shall be performed before
sending the compressor to the suppliers.
Only the electrical heating to the compressor body is
allowed to accelerate the process.
Oil shall be drained safely from the system.
For installation with handling the refrigerant (R-32),
use dedicated tools and piping materials. Because the
pressure of the refrigerant, R-32 is approximately 1.6 times
higher than that of R-22, failure to use the dedicated
tools and piping materials may cause rupture or injury.
Furthermore, it may cause serious accidents such as water
leakage, electric shock, or fire.
6
English
Never install a motor-driven equipment to prevent
ignition.
Power supply line, fuse, or circuit breaker
Be sure not to perform power cable modification,
extension wiring, and multiple wire connection.
It may cause electric shock or fire due to poor
connection, poor insulation, or current limit
override.
When extension wiring is required due to power
line damage, refer to "Step 2-5 Optional: Extending
the power cable" in the installation manual.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents