Installation Mounting The Fan Coil Unit; Horizontal Installation - Daikin FWE03D Series Installation Manual

Fan coil units
Hide thumbs Also See for FWE03D Series:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 3
Electrical characteristics
Phase
Frequency
Voltage range
Voltage tolerance
Maximum running current
Overcurrent fuse
Specifications for field wiring
Wire
Size (mm²)
(a)(b)
Power supply
H05VV-U3G
According to the
wiring
applicable
legislation ≤4.0
Remote
Sheathed wire 2
0.75~1.25
(c)
controller and
conductors
unit
transmission
wiring
(a)
Only in case of protected pipes. Use H07RN-F in case
of no protection.
(b)
Run electrical wiring through a conduit to protect against
external forces.
(c)
Use double insulation wire for remote controller (sheath
thickness ≥1 mm) or run wires through a wall or conduit
so that the user cannot come in contact with them.
(d)
The length shall be the total extended length in a system
with group control.
5
Installation
5.1
Mounting the fan coil unit
INFORMATION
The spacing between ceiling and unit should be ≥10  mm
and the suction space should be ≥150 mm.
INFORMATION
All the above parts are field supplied. For installation other
than standard installation, contact your local dealer for
advice.
5.1.1

Horizontal installation

1 Make the required ceiling opening for installation in an
applicable place.
It may be necessary to reinforce the suspended ceiling frame
to keep the ceiling level and to prevent it from vibrating.
Consult the builder for details.
2 Install the suspension bolts. Use either W3/8 or M10 size bolts.
Use anchors for existing ceilings, and a sunken insert, sunken
anchors or other field supplied parts for new ceilings to
reinforce the ceiling in order to bear the weight of the unit. Refer
to it to check for points requiring reinforcing. Adjust the
clearance from the ceiling before proceeding further.
FWE03~11D
Fan coil units
3P443944-5E – 2019.09
FWE-D
1N~
50 Hz
220~240 V
±10%
0.46 A
16 A
Length
3 Install the unit temporarily.
Attach the hanger bracket to the suspension bolt. Fix the unit
(d)
securely.
≤500 m
4 Adjust the unit to the correct position for installation.
10≤
5 Check if the unit is horizontally levelled.
Do not install the unit tilted. If the unit is tilted against the
direction of the condensate flow (drain piping side raised), it
will cause water to drip.
Check if the unit is levelled at all 4 corners with a water level
or a water-filled plastic tube.
10≤
5 Installation
e
a
Ceiling slab
b
Anchor
c
Long nut or turn-buckle
d
Suspension bolt
e
Suspended ceiling
a
b
c
d
a
Nut (field supply)
b
Washer (field supply)
c
Hanger bracket
d
Double nut (field supply)
1/100
b
a
a
Plastic tube
b
Level
a
b
c
d
Installation manual