Installation; Selection The Best Location; Front View - LG MULTI V JRNU28GBGA3 Installation Manual

Ceiling concealed duct - high static
Table of Contents

Advertisement

Installation

Read completely, then follow step by step.
Selection of the best location
• The place shall easily bear a load exceeding four times the indoor unit's weight.
• The place shall be able to inspect the unit as the figure.
• The place where the unit shall be leveled.
• The place shall allow easy water drainage.(Suitable dimension "H" is necessary to get a slope to drain as
figure.)
• The place shall easily connect with the outdoor unit.
• The place where the unit is not affected by an electrical noise.
• The place where air circulation in the room will be good .
• There should not be any heat source or steam near the unit.
CAUTION : In case that the unit is installed near the sea, the installation parts
may be corroded by salt, The installation parts (and the unit) should be taken
appropriate anti-corrosion measures.
[Inspection Hole Standard]
Number of
Inspection hole
1
2
Hole size should be
more than the size of IDU.
Top view
Inspection hole
(unit: mm)
Control box
600

Front view

Distance between
False ceiling & Actual ceiling
More than 100cm
20cm to 100cm
Less than 20cm
(600X600)
600
Front
H
Remarks
Sufficient space in the ceiling for servicing.
Insufficient space. Difficult for servicing
Minimum height for motor replacement.
Installation
Installation Manual 7