Checking the electrical connections

Check all electrical connections for firm seating.

Checking the gas type

1. Check with your gas supply utility regarding the
gas type and Wobbe index W
1013.25 mbar).
The boiler can be operated in the following Wobbe
index ranges:
With natural gas E:
Wobbe index range 12.0 to 16.1 kWh/m
3
58.0 MJ/m
)
With natural gas LL:
Wobbe index range 10.0 to 13.1 kWh/m
47.2 MJ/m
3
)
With control cables also check:
2. In the delivered condition, the burner is set up for
(0 °C;
s
3. Record the gas type in the report on page 62.
3
(43.2 to
3
(36.0 to
Commissioning, inspection, maintenance
Connection and kink-free routing
Application and seating of retaining clips
natural gas E. If required, change the gas type set-
ting to natural gas LL: See chapter "Setting the gas
type", page 12