Description
3.4 Parameterization
M08 Limit thresholds (LIMn, n = 1 to 4)
Note
This menu is divided into 4 sections for limit thresholds LIM 1 ... 4.
P08.n.01
P08.n.02
P08.n.03
P08.n.04
P08.n.05
P08.n.06
P08.n.07
P08.n.08
P08.n.09
P08.n.10
P08.n.01
P08.n.02
P08.n.03,
P08.n.04
P08.n.05
P08.n.06,
P08.n.07,
P08.n.08
P08.n.09
P08.n.10
34
Reference measure
Function
Upper threshold
Multiplier
Delay
Lower threshold
Multiplier
Delay
Status
Reset mode
Defines the multimeter measurement to which the limit threshold applies.
Defines the function of the limit threshold.
• Max = LIMn active if the measurement exceeds P08. P08.n.03 is the reset
threshold.
• Min = LIMn active if the measurement falls below P08. P08.n.06 is the reset
threshold.
• Min + Max = LIMn active if the measurement exceeds P08.n.03 or falls
below P08.n.06.
Defines the upper threshold resulting from the multiplication of the value
P08.n.03 by P08.n.04.
Triggering delay for upper threshold.
As above, but relating to the lower threshold.
Permits inversion of the status of limit threshold LIMn.
• ON: You must manually save and reset the threshold value.
• OFF: The threshold value is saved and reset automatically.
Unit
Default
Range
–
OFF
OFF ... (measures)
Max
•
•
•
0
−9999 ... +9999
x1
x0.01 ... x10k
s
0
0.0 ... 1000.0
–
−9999 ... +9999
x1
x0.01 ... x10k
s
0
0.0 ... 1000.0
–
OFF
•
•
Manual, 08/2018, 2514284149-01
Max
Min
Max + Min
OFF
ON
7KT multimeter