Indoor unit
a Factory refrigerant charge of the product: see unit name plate .
b Additional refrigerant amount charged in the field . (Refer to the above information for the quantity of
NOtE
refrigerant replenishment . )
c Total refrigerant charge .
d Refrigerant cylinder and manifold for charging .
• The filled-out label must be adhered in the proximity of the product charging port .
(ex . onto the inside of the stop valve cover)
CaUtION

Check and test operation

1 . Supply power to the air conditioner .
2 . Turn on the air conditioner .
3 . While pressing and holding the Set/Cancel button on the remote controller, press the Power
display the temperature of indoor heat exchanger .
- Write down the displayed temperature .
4 . Press the turbo button on the remote controller to operate in turbo mode for 10 minutes .
5 . Check if the indoor unit is operating normally .
- Standard condition to judge normal operation . (Indoor/outdoor unit over 21 °C, operate in Cool mode for over 10
minute)
6 . While pressing and holding the Set/Cancel button on the remote controller, press the Power
display the temperature of indoor heat exchanger .
- If the displayed temperature differs over 10 °C from the temperature written down previously, it is operating normally .
7 . When checking above step 1~6 is done, tell the user how to use the air conditioner .

Pump down procedure (When removing the product)

1 . Press the Power
button on the indoor unit control panel for 5 seconds to enter the Pump down mode and operate
the compressor for over 5 minutes . Or, Press the Set/Cancel, Mode and temp - button on the remote controller
simultaneously to enter the Pump down mode and operate the compressor for over 5 minutes .
2 . Remove the High/Low pressure side valve cap .
3 . Use the L wrench to completely close the valve on the high pressure side .
4 . After 2 minutes, completely close the valve on the low pressure side .
5 . Press the Power
button on the indoor unit control panel for 5 seconds to deactivate the Pump down mode . Or, Press
the Set/Cancel, Mode and temp - button on the remote controller simultaneously to deactivate the Pump down mode .
6 . Disconnect the pipe .
2
d
Outdoor unit
1
ENGLISH-23
Unit
kg
, a
1
2 , b
+ 2
, C
1
refrigerant type
R-410A
• GWP=Global Warming Potential
• Calculating tCO2e : kg x GWP / 1000
tCO2e
GWP value
2088
button for 3 seconds to
button for 3 seconds to