INNCOM e7w THERMOSTAT USER GUIDE
6. Press the FC button to return to SERVICE MODE or press UP arrow button to display
next mode.
Or
Press the FC button twice to exit SERVICE MODE
ADR – Teaching A Device Address (Adr)
Adr parameter is used to bind the target device to the Room ID, PAN ID, and RF channel configured in
the e7w, while at the same time setting the target device address to the displayed Adr value.
Follow the steps below to configure Adr parameter:
NOTE: Before user start configuring ADR mode, user need configure Room ID, PAN ID and RF Chan-
nel in the e7w, if not already done.
1. Enter SERVICE MODE
2. Use the UP/DOWN arrow buttons to select Adr.
3. Press MODE button. This action displays preconfigured Adr address
4. Use the UP/DOWN arrow buttons to change Adr value to the desired address.
5. Press FAN to initiate a reverse bind
or
Press MODE to initiate a forward bind

Reverse Binding

Reverse binding is supported by device such as PC502.4G, S541.RF, K594/K595.RF.
To configure reverse binding, follow the steps below.
31-00302-01
32