9.4.2

Switch-on delay / switch-off delay

For the logic output, a switch-on delay and switch-off delay can be set.
Main menu > Commissioning > Settings > ... or
Main menu > Settings > Logic functions > Logic 1...10 >
Operating line
Switch-on delay
Switch-off delay
* See reference on time format in Sec. 9.2.
The switch-on delay always acts on the switch-on command, the switch-off delay
on the switch-off command.
9.4.3

Minimum on-time

For the logic output, a minimum switch-on delay can be set. In other words, the
output remains switched on for the set time if a switch-on command arrives.
Main menu > Commissioning > Settings > ... or
Main menu > Settings > Logic functions > Logic 1...10 >
Operating line
On time minimum
* See reference on time format in Sec. 9.2.
The minimum on-time always takes effect after a switch-on command.
9.4.4

Minimum off-time

The minimum off time prevents aggregates from cycling too frequently.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Logic functions > Logic 1...10 >
Operating line
Off time minimum
* See reference on time format in Sec. 9.2.
The minimum off time always takes effect after a switch-off command.
9.5

Operation selector

The operating mode of the output can be preselected via the operation selector in
the main menu.
Logic blocks are preselected and the current state is displayed. Switch-on and
switch-off delay as well as minimum on and off time are considered.
Main menu > Operation selector 1...10 >
Operating line
Preselection
State
Central control unit RMB795B
Logic
Range
00.00...59.59 m:s or*
00.00...23.50 h:m.
00.00...59.59 m:s or*
00.00...23.50 h:m.
Range
00.00...59.59 m:s or*
00.00...23.50 h:m.
Range
00.00...59.59 m:s or*
00.00...23.50 h:m.
Comments
Auto, Off, On.
Display of the current state: Off, On.
Factory setting
00.00 m:s
00.00 m:s
Factory setting
00.00 m:s
Factory setting
00.00 m:s
CE1P3122en
18.01.2012