Turn Off The Water Heater; Installation, Maintenance And Service Part; Introduction; About The Water Heater - Lochinvar AMP 200-9 Installation, Commissioning, User & Maintenance Instructions

Cavalier
Table of Contents

Advertisement

Caution
Preferably the temperature control knob, on each
thermostat, should be set to 60°C.
Harmful scaling and lime build-up will be higher
when using position 65°C and higher. At lower
temperature settings there is a higher risk of high
legionella concentrations in the water.
4.2

Turn off the water heater

2.2.1 Turn off for a short period
To turn off the water heater for less than 2
months, set the water heater in the O FF mode
(see 3.2.1.1).
2.2.2 Turn off for a long period
When the water heater needs to be turned off for
more than 2 months, contact your service and
maintenance engineer to decommission the
water heater.
Installation, Maintenance
and Service Part
5

Introduction

5.1

About the water heater

The AMP water heater is intended for heating
water for sanitary purposes.
The AMP is a electric storage water heater. The
electric heating elements transfer their heat
directly to the water.
5.2

Working principle

Cold water enters the tank through the water
inlet. When the water temperature drops beneath
the set temperature, the electrical heating
elements are activated and the water is heated.
The heating elements directly transfer the heat to
the water and the hot water leaves the tank
through the water outlet.
8
The tank of the water heater has to be
completely filled during operation. The tank at
least must remain under mains water supply
pressure at any time. Fresh cold water is
immediately added when hot water is drawn from
the water heater. The regulation thermostat on
each heating element, is equipped with a contact
thermostat. This thermostat measures the water
temperature, on the outside of the tank.
6

Safety

6.1

Safety instructions

For safety instructions on the use of the water
heater, refer to Safety (see 2) in the User part of
this manual.
Warning
Installation, maintenance and service must be
carried out by a qualified engineer in compliance
with the national and local regulations.
Warning
This appliance must be installed on a non-
flammable floor or surface.
Caution
The water heater may only be moved in an
upright position. After unpacking, make sure that
the water heater is not damaged.
Caution
Fill the water heater completely before use. Dry
firing will damage the water heater.
Note
Any leakage from the tank and/or connections
can cause damage to the immediate
environment or floors below the level of the
installation room. Install the water heater above a
waste water drain or in a suitable metal leak tray.
The leak tray must have an appropriate waste
water drain and must be at least 5 cm deep with
a length and width of at least 5 cm larger than
the water heater.
Installation, Commissioning, User & Maintenance Instructions