ABB Arc Guard System TVOC-2 Installation And Maintenance Manual page 34

Hide thumbs Also See for Arc Guard System TVOC-2:
Table of Contents

Advertisement

34
ABB
ARC GUARD SYSTEM™ – T VOC-2 INSTALL ATION AND MAINTENANCE GUIDE
Step 3: Confirming connected modules
This is the third step to make the system work after
installing the Arc Monitor. Use this procedure to confirm
connected modules during start up.
In window, 3.1.1 View connected do the following:
1.
Check the list of modules and if all modules are
included, press Yes.
2.
If all modules not are included, press No. See next
step 3, below.
WARNING
Make sure that supply voltage is switched off!
3.
Remove the power and check the connections to
the modules.
4.
Power on.
Start-Up sequence will start again with step 1. See:
5.
"Step 1: Setting menu language" on page 33.
Step 4: Checking DIP Switches
This is the fourth step to make the system work after
installing the Arc Monitor. Use this procedure to check the
DIP switches.
In window, 3.2 View DIP Switch do the steps below:
1.
Check the DIP Switch and scroll with right arrow to
next switch.
2.
Check through all DIP switches menus.
3.
The last switch menu, 3.2 View DIP display,
4.
DIP Switch OK? If all DIP Switches are OK, press Yes.
5.
If some of the DIP switches are not OK, Press NO.
See next step 6, below.
WARNING
Make sure that supply voltage is switched off!
6.
Remove power and check the DIP switch.
7.
Power on.
8.
Start-Up sequence will start again with step 1. See:
"Step 1: Setting menu language" on page 33.
Step 5: Final confirmation
This is the fifth step to make the system work after
installing the Arc monitor. Use this procedure to confirm
that all Start-Up settings are done.
In the Start-up menu do the steps below:
1.
Press OK. All settings done. The system is now
ready to run accordingly and will return to Start
window.
2.
Check that the green LEDs "Power" on left side of
extension modules on Arc Monitor is lit.
3.
Check that the Green LED "Power" on HMI is lit.
4.
Check that HMI is showing text.
3.2 View DIP
DIP Switch OK?
10 10 01 00
Switches are not used
N
o
Figure 39
Checking DIP switches
Y
e
s
1SFC170011M0201

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents