2TMD041900D0015
21.10.2019
Product manual
ABB-Welcome IP
H8131.P.-. , H8131.P.-.-02
H8136.P.-. , H8136.P.-.-02
Mini video outdoor station

Advertisement

Table of Contents
loading

Summary of Contents for ABB Welcome IP H8131.P. Series

  • Page 1 │ 2TMD041900D0015 21.10.2019 Product manual ABB-Welcome IP H8131.P.-. , H8131.P.-.-02 H8136.P.-. , H8136.P.-.-02 Mini video outdoor station...
  • Page 2: Table Of Contents

    Table of contents Notes on the instruction manual ........................4 Safety ................................4 Intended use ..............................5 Environment ..............................6 ABB devices ............................6 Product description ............................7 Control elements ..........................7 Terminal description ........................... 8 Lock type and connection ........................9 Technical data .............................
  • Page 3 Table of contents 8.4.1 Assigning ID authentications to a user ...................44 8.4.2 Assigning the locks to a user ......................47 8.4.3 Removing ID authentications from a user ..................48 FCC ................................49 Cyber security .............................. 50 10.1 Disclaimer ............................50 10.2 Performance and service ......................... 50 10.3 Deployment guideline ........................
  • Page 4: Notes On The Instruction Manual

    Please keep this manual in a safe place. If you pass the device on, also pass on this manual along with it. ABB accepts no liability for any failure to observe the instructions in this manual. Safety...
  • Page 5: Intended Use

    Intended use Intended use As part of the ABB-Welcome IP system, this device can only be used with accessories from that system. │5 Product manual 2TMD041900D0015...
  • Page 6: Environment

    ABB devices All packaging materials and devices from ABB bear the markings and test seals for proper disposal. Always dispose of the packing materials and electric devices and their components via an authorized collection facility or disposal company.
  • Page 7: Product Description

    Product description Product description Control elements Description Indicator flashes slowly: ringing Indicator flashes quickly: busy line Call indicator Unlock indicator Speaker and microphone integration Round pushbutton │7 Product manual 2TMD041900D0015...
  • Page 8: Terminal Description

    Product description Terminal description EXIT AGND LOCK NC COM NO GND DC+ Description Connector for the sensor used for door status detection Connector for exit button Plug-in clamps (LOCK...AGND) for door opener Plug-in clamps (COM...NC...NO) for floating output Plug-in clamps (DC+...GND) for standalone power supply LAN (PoE) │8 Product manual 2TMD041900D0015...
  • Page 9: Lock Type And Connection

    Product description Lock type and connection Lock type Operation type Voltage Wiring type Electrical strike ⎓ Power on to open Type A/B 12 V lock, 12V Electrical strike ⎓ Type B Power on to open 24 V lock, 24V Electrical rim ⎓...
  • Page 10: Technical Data

    Technical data Technical data Designation Value ⎓ Rating voltage 24 V ⎓ Operating voltage range 20-27 V ⎓ 27 V , 310 mA Rating current ⎓ 24 V , 350 mA Operating temperature -40 °C…+55 °C 99 mm x 168 mm × 26 mm (H8131.P.-.) Product dimensions 105 mm x 180 mm ×...
  • Page 11: Mounting/Installation

    Mounting/Installation Mounting/Installation Warning Electric voltage! Dangerous currents flow through the body when coming into direct or indirect contact with live components. This can result in electric shock, burns or even death. – Disconnect the mains power supply prior to installation and/or disassembly! –...
  • Page 12: Preparation

    Mounting/Installation Preparation Use gloves to protect yourself from being cut. Installation height 1 50 m 5 feet Wiring │12 Product manual 2TMD041900D0015...
  • Page 13: Surface-Mounted Installation

    Mounting/Installation Surface-mounted installation Product dimension 99 mm 26.5 mm 78 mm 62 mm 60 mm Surface-mounted on the wall Mounting screw x 4 ⌀ Screw shaft: Scre w le ngth: 25 mm ≥ │13 Product manual 2TMD041900D0015...
  • Page 14 Mounting/Installation Surface-mounted on the box (e.g. VDE box) Mounting screw x 4 ⌀ Screw shaft: Scre w le ngth: ≥ 25 mm │14 Product manual 2TMD041900D0015...
  • Page 15: Flush-Mounted Installation

    Mounting/Installation Flush-mounted installation Product dimension 99 mm 45 mm 105 mm 53 mm 99 mm Flush-mounted with pre-installation box Mounting screw x 4 ⌀ Screw shaft : Scre w le ngth: ≥ 25 mm │15 Product manual 2TMD041900D0015...
  • Page 16: Cavity Wall Installation

    Mounting/Installation Cavity wall installation Product dimension 92 mm 105 mm 43 mm 90 mm 97 mm Mounting Mounting screw x 4 ⌀ Screw shaft: Scre w le ngth: ≥ 25 mm │16 Product manual 2TMD041900D0015...
  • Page 17: Replacing The Nameplate

    Mounting/Installation Replacing the nameplate │17 Product manual 2TMD041900D0015...
  • Page 18: Installation Situation

    Mounting/Installation Installation situation Note The following installation situations must be avoided without fail to ensure picture quality: ■ Direct light ■ Direct sunlight ■ Extremely bright picture background ■ Highly reflective walls on the opposite side of the door station ■...
  • Page 19: Commissioning

    Commissioning Commissioning Configure the settings on indoor station 8.1.1 Outdoor station enters engineering mode Note The mini outdoor station must be in the same network with the indoor station. Unlock indicator First pushbutton Pushbutton module Please follow the steps below, ■...
  • Page 20: Indoor Station Enters Engineering Settings

    Commissioning 8.1.2 Indoor station enters engineering settings On the extra screen of indoor station, click "System" to access the corresponding screen. On the "System settings" screen, click "Engineering settings", enter the engineering password and then click "Outdoor station settings" to access the corresponding screen. │20 Product manual 2TMD041900D0015...
  • Page 21: Device Settings

    Commissioning 8.1.3 Device settings On the "Outdoor station settings" screen, select the device type = "2nd OS". [1] Location = Internal With this setting, 2nd OS is connected to the router in the apartment. │21 Product manual 2TMD041900D0015...
  • Page 22 Commissioning [2] Location = External With this setting, 2nd OS is connected to the switch outside the apartment. Note The external and internal types cannot be used in mixed scenarios in the same apartment. │22 Product manual 2TMD041900D0015...
  • Page 23: Lock Management

    Commissioning 8.1.4 Lock management On the "Outdoor station settings" screen, Function Unlock type when swiping Set the lock to be released when swiping. ■ Default lock (default) ■ Subsidiary lock. Lock type Set the lock type for the default lock and subsidiary lock. ■...
  • Page 24: Door Status Detection

    Commissioning 8.1.5 Door status detection Go to the "Outdoor station settings" screen. Function Door status detection If this function is enable, the outdoor station will send an alarm to the management software if the door is open longer than 120 s (A sensor should first be connected to the outdoor station). Tamper proof alarm If this function is enabled, the outdoor station will send an alarm to the management software if the outdoor station is removed from the wall.
  • Page 25: Sound

    Commissioning 8.1.6 Sound Got to the "Outdoor station settings" screen. Function Volume of outdoor station Click "+" or "-" to adjust the ringtone volume and the voice volume on the outdoor station. Button tone Tick the checkbox to enable button tones on the outdoor station. Voice prompt ■...
  • Page 26: Anti-Ficker Setting

    Commissioning 8.1.7 Anti-ficker setting On the "Outdoor station settings" screen, select the refresh rate from the drop-down list. │26 Product manual 2TMD041900D0015...
  • Page 27: Set The Function Of Pushbutton

    Commissioning 8.1.8 Set the function of pushbutton On the "Outdoor station settings" screen, click "Pushbutton address setting" to access the settings of the pushbuttons. Note Device no. should be entered if "Phone guard unit" is selected. │27 Product manual 2TMD041900D0015...
  • Page 28: Time Sync Setting

    Commissioning 8.1.9 Time sync setting On the "Outdoor station settings" screen. If "Sync time with management" is selected, the outdoor station will sync the time from the management software. If "Close time sync" is selected, the time and date needs to be set manually. │28 Product manual 2TMD041900D0015...
  • Page 29: Compatible Mode Setting

    Commissioning 8.1.10 Compatible mode setting On the "Outdoor station settings" screen, the outdoor station is set to "Security mode" by default (Compatible mode = off). │29 Product manual 2TMD041900D0015...
  • Page 30: Firmware Update

    Commissioning 8.1.11 Firmware update Note The outdoor station doesn’t need to enter engineering mode when you want to upgrade the firmware. On the "Outdoor station settings" screen, click "Firmware update", select the outdoor station and the file from SD card, then click "OK" to update the firmware. │30 Product manual 2TMD041900D0015...
  • Page 31: Version Information

    Commissioning 8.1.12 Version information On the "Outdoor station settings" screen, view the version information. │31 Product manual 2TMD041900D0015...
  • Page 32: Serial Number

    Commissioning 8.1.13 Serial number On the "Outdoor station settings" screen, view the serial number, this number is used to get the signature from the management software. │32 Product manual 2TMD041900D0015...
  • Page 33: Signature

    Commissioning 8.1.14 Signature On the "Outdoor station settings" screen, view the signature. │33 Product manual 2TMD041900D0015...
  • Page 34: Configure The Settings On Smartap

    Commissioning Configure the settings on SmartAP 8.2.1 Add mini outdoor station Note Only a mini outdoor station without a certificate can be added by SmartAP. This mini outdoor station will lose its certificate if its physical address is changed. The mini outdoor station needs to be powered on before being added. On the configuration screen of SmartAP, following the steps below, Note If the mini outdoor station is installed in the community network.
  • Page 35: Configure The Settings

    Commissioning 8.2.2 Configure the settings On the configuration screen, click "Door entry system", "Outdoor stations", then click a mini outdoor station to access the settings. │35 Product manual 2TMD041900D0015...
  • Page 36 Commissioning Basic information Function Device ID Click the icon to return to the previous screen Overview of the outdoor station Device type of the outdoor station Display the address of the outdoor station Display the serial number of the outdoor station Display the version of the outdoor station │36 Product manual 2TMD041900D0015...
  • Page 37 Commissioning Addtional settings Funciton Set the physical address for the outdoor station Set the unlock time for default lock and subsidiary lock. Enable or disable the time synchronization with the management software. Update the firmware via local PC. Update the firmware via the external website. Set the trusted devices for the outdoor station.
  • Page 38 Commissioning Set the door lock time It the default lock type is set to "IP actuator", following the steps below, │38 Product manual 2TMD041900D0015...
  • Page 39 Commissioning On the designated IP actuator screen, following the steps below, │39 Product manual 2TMD041900D0015...
  • Page 40 Commissioning │40 Product manual 2TMD041900D0015...
  • Page 41 Commissioning Set the trusted devices On the designated mini outdoor station screen, following the steps below, Note You need to enable the "Trust this management software" function if you want this outdoor station to unlock in the event of an emergency. │41 Product manual 2TMD041900D0015...
  • Page 42: Card Management On Mini Outdoor Station

    Commissioning Card management on mini outdoor station Note It is recommended that ID cards are created and maintained using local outdoor station or management software only. Programming The system will take the first card swiped after powering up the system within 60s as the admin card.
  • Page 43 Commissioning During setting, please swipe the same admin card. Function Action Unlock indicator Swipe admin card 1x or no Exit settings cards swiped within 15 seconds Function Action Unlock indicator Open a door Swipe the enrolled keycard Green Press and hold the 1st button for 3 LED: flash green 3 s to enter configuration mode.
  • Page 44: Card Management On Smartap

    Commissioning Card management on SmartAP 8.4.1 Assigning ID authentications to a user On the designated user screen, following the steps below, │44 Product manual 2TMD041900D0015...
  • Page 45 Commissioning Registered ID authentications by card no. When multiple card numbers are registered, the card numbers are separated using ",". │45 Product manual 2TMD041900D0015...
  • Page 46 Commissioning Register by outdoor station (recommend) Swipe the ID authentications before the outdoor station when the prompt window appears. │46 Product manual 2TMD041900D0015...
  • Page 47: Assigning The Locks To A User

    Commissioning 8.4.2 Assigning the locks to a user The ID cards assigned to this user can release all the locks assigned to this user. Note A maximum of 64 ID cards can be supported by mini outdoor station. If more than 64 ID cards have registered by the user, you can’t assign the mini outdoor station to this user.
  • Page 48: Removing Id Authentications From A User

    Commissioning 8.4.3 Removing ID authentications from a user On the designated user screen, following the steps below, │48 Product manual 2TMD041900D0015...
  • Page 49: Fcc

    FCC ID: 2AEBL-H8131 This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Only operate the device in accordance with the instructions supplied.
  • Page 50: Cyber Security

    H8131.P.-. product, the network, its system and interfaces against any kind of security breaches, unauthorized access, interference, intrusion, leakage and/or theft of data or information. ABB and its affiliates are not liable for damages and/or losses related to such security breaches, unauthorized access, interference, intrusion, leakage and/or theft of data or information.
  • Page 51: Deployment Guideline

    The H8131.P.-. device is not susceptible to malware, because custom code cannot be executed on the system. The only way to update the software is via firmware upgrades. Only firmware signed by ABB can be accepted. │51 Product manual 2TMD041900D0015...
  • Page 52 We reserve the right to at all times make technical changes as well as changes to the contents of this document without prior notice. The detailed specifications agreed to at the time of ordering apply to all orders. ABB accepts no responsibility for possible errors or incompleteness in this document.
  • Page 53 Km 9 National Highway 1A , The detailed specifications agreed P.O.Box 11070 Dubai-UAE Hoang Liet, Hoang Mai, Hanoi, upon apply for orders. ABB accepts T : +971 4 3147 586 Vietnam no responsibility for possible errors F : +971 4 3401 541 T : +84 4 3861 1010 or incompleteness in this document.
  • Page 54 Error! Use the Home tab to apply Überschrift 1 to the text that you want to appear here. © Copyright 2019 ABB All rights reserved │54 Product manual 2TMD041900D0015...