Step 9 Optional: Installing Dpm - Samsung AC MXADKH Series Installation Manual

Table of Contents

Advertisement

Installation Procedure

Step 9 Optional: Installing DPM

DPM allowable Outdoor and indoor unit models
DPM allowable Outdoor and indoor unit models
Outdoor unit models
AC071MXADKH
❋ ❋ Installation of multiple indoor units should consist
of units that have the same capacity.
e.g.
When you install the AC071MXADKH outdoor
unit as DPM combination such as 2 indoor
units connection, only the combination on the
table is available.
Connecting communication line and wired remote controller
In case of 2 indoor units connection
1 phase 2 wire
L/N
Outdoor
(220V - 240V)
unit
❋ ❋ The wired remote controller can be used with any of the DPM indoor units.
Operation and specification
f The two, the three, or the four sets of the indoor units with DPM installation which are controlled by wired
f
and wireless remote controller work equally. (All controls such as ON/OFF, cooling/heating/dehumidification/
ventilation, high/ medium/low wind.)
f Thermo OFF which stops when indoor temperature reaches set temperature works by the average sensor value
f
of the indoor temperature of the all indoor units.
f When one of the several indoor units has a problem, they protect operation or stop working.
f
Instruction for installation and operation
f You should install the DPM according to the above installation specification and eliminate the factors that give electrical
f
load to the both indoor units when installing and operating. (Heater / window / front door / ventilation / partition that
divides space)
f You should provide sufficient instructions about the operation method and specification features to users and fill in caution
f
phrases on wired remote controller when necessary.
- <The air-conditioners in this area are special type to be controlled simultaneously.>
20
English
2 indoor units connection
Indoor unit
AC035MN1DKH
AC035MNNDKH
AC035MNMDKH
AC035MNLDKH
AC035MNJDKH
AC035MNADKH
F1/F2
F1/F2
Indoor unit #1
L/N
L/N
1 phase 2 wire
(220V - 240V)
Space requirements for indoor and outdoor
units and piping installation
(Refer to page 15 installation specification.)
f Two indoor units should be installed in one area
f
which is not divided by a wall.
f The distance between two indoor units should be
f
within a straight-line of 10m.
f After branching, the distance between the piping
f
connected to the two indoor units should be within
5m.
f The height difference between two units should be
f
within 0.5m.
f Use the joint KIT that is only for DPM. (Please refer
f
to the table below)
2-Indoor units
connection
DPM KIT
MXJ-2D2509K MXJ-3D2509K MXJ-4D2509K
F1/F2
Indoor unit #2
L/N
Remote control
3-Indoor units
4-Indoor units
connection
connection