12.2 Input and Output Terminals Configuration

12.2.1 Digital Input Configuration

4 multi-function digital inputs are available with PNP and NPN wiring.
Code
Name
E1.00
X1 input
E1.01
X2 input
E1.02
X3 input
E1.03
X4 input
0: Inactive
1: Multi-speed control input 1
2: Multi-speed control input 2
3: Multi-speed control input 3
8 multi-speeds are available by combination of 4 terminals, see
the setting frequency by multi-speed function" on page
10: Acceleration / deceleration time 1 activation
11: Acceleration / deceleration time 2 activation
12: Acceleration / deceleration time 3 activation
Used to switch between 8 groups of acceleration / deceleration time, see
ter 12.4.3 "Acceleration and Deceleration Configuration" on page
15: Freewheeling stop activation
'Freewheeling stop activation' generates a stop command and forces the fre-
quency converter to freewheel to stop regardless of the stopping mode con-
figured by E0.50.
16: Stop DC-braking activation
This function is used when stopping mode is set with [E0.50] = '0: Decelerat-
ing stop'.
See
chapter 12.5.5 "Stop Behavior Setting" on page 116
20: Frequency Up command
21: Frequency Down command
22: Up / Down command reset
Used to change the output frequency, see
by digital input Up / Down command" on page
23: Torque / speed control switch
25: 3-wire control
DOK-RCON04-VFC3210****-IT01-EN-P
Functions and Parameters
Setting range
0...51
97.
chapter "Adjust the setting frequency
95.
Bosch Rexroth AG
Default
Min.
Attri.
35
Stop
36
Stop
0
Stop
0
Stop
chapter "Adjust
chap-
102.
79/253