Updating firmware of mimic display driver
FT2001-A1
WARNING
Incorrect assignment between detector/detector group and customer text
Misleading messages in the event of an alarm
Never change the wiring during the firmware update.
The firmware must be updated individually for each mimic display driver.
Preparation
The mimic display driver is fed by a 24 V external power supply or by the C-
NET detector line.
The driver for the MCL-USB adapter FDUZ221 is installed on the PC.
1. Select 'File' > 'Import new FW package'.
2. Open an F-FXS7211-XX_x_x_...zip file that matches the 'Site' in the selection
window.
3. Connect the PC to the device via the MCL-USB adapter.
FT2001-A1
X2
Connection of the PC to the mimic display driver
FDUZ221 MCL-USB adapter (interface USB/MC-LINK)
X2
Connection for the MCL-USB adapter
FT2010
Mimic display driver
Updating the firmware
1. Select 'Update' > 'FW update standard peripheral device'.
The 'FW update standard peripheral device' window opens.
Cerberus-Engineering-Tool establishes the connection to the device and
sets the device to update mode.
The latest firmware package and the latest firmware version are suggested.
2. Select the firmware package that matches the 'Site'.
3. Click on 'Start'.
The status bar indicates the update progress.
Updating the firmware of the peripheral devices

Updating firmware of mimic display driver FT2001-A1

USB
MC-Link
FDUZ221
21
93
A6V10210416_f_en_--
14.01.2013