COMPACT I/O MODULE
This includes, for example:
• Qualification to connect the device according to applicable
specifications and regulations, and a qualification to put
this device into operation, to power it down, or to activate it
by respecting the internal directions.
• Knowledge of safety rules.
• Knowledge about application and use of the device within
the equipment system.
BEFORE INSTALLATION
1. Unpack the XIO-10HUB Extension Module.
2. Check the equipment and report any damage to a Hon-
eywell representative.
3. Read all of these instructions and ensure they are
understood.
MOUNTING
Mount the XIO-10HUB Extension Module on standard DIN rail
per DIN EN 50022 (1.35 x 0.3 in. [35 x 7.5 mm]), in junction
boxes and/or on distribution panels.
INSTALLATION
CAUTION
Electrical installation and device termination shall
be accomplished by qualified persons only, by
respecting all applicable specifications and
regulations.
1. Power down the equipment. Mount the Extension mod-
ule on the DIN rail.
1a
M25060
2. Plug in the terminal block for bus connection.
2a
M25062
95-7717—2
1b
M25061
2b
M25063
2
3. Prepare the cable for bus connection:
0.2 in.
(5 mm)
3a
M25040
a. Remove about 0.75 in. (2 cm) of the plastic cable
sheath.
b. Strip 0.2 in. (5 mm) insulation from each wire. Put a
wire end sleeve on stranded wires.
c. Insert the wire to the respective contact and secure
it by screwing down the contact screw.
d. Wire cross section of the 4 pole terminal block bus/
mains connection:
(1) Maximum 16 AWG (1.5 mm
(2) Maximum 18 AWG (1.0 mm
(3) Wire diameter minimum 28 AWG (0.3 mm) up to
16 AWG (1.4 mm).
4. Prepare cable for module connections.
0.3 in.
(7 mm)
4a
M25041
a. Strip the wires by 0.3 in. (7 mm). Put a wire end
sleeve on stranded wires.
b. Insert the wire into the respective module contact
and secure it by screwing down the contact screw
with a screwdriver.
c. Wire cross section of the 4 pole terminal block
bus/mains connection:
(1) Maximum 12 AWG (4.0 mm
(2) Maximum 14 AWG (2.5 mm
(3) Wire diameter: minimum 28 AWG (0.3 mm) up to
maximum 10 AWG (2.7 mm).
5. The module can be aligned without interspace. Use the
strapping plug to connect bus and supply voltage when
the modules are mounted in series. The modules can
be mounted in series without interspace. The maximum
number of modules connected in series is 15, with each
group needing an external power supply.
+24V
GND
E1
E2
5a
M25066
3b
M25064
2
) single wire.
2
) stranded wire.
4b
M25065
2
) single wire.
2
) stranded wire.
+24V
GND
E1
E2
5b
M25067