L909X-Series Electrified Mortise Lock,
LM929X-Series Electrified Two-Point Lock
Wiring Instructions and Specifications
L-Series Electrified Lock
All installations should be in accordance with local electrical codes and national electrical code, NFPA 70.
L909X-Series and LM929X-
Series electrified locks offer
selection between one of
two modes, EL or EU.
Select the appropriate mode
for the installation using the
mode select switch located
on the mortise chassis.
EL, electrically locked
(fail safe):
Outside knob/lever or both
outside and inside knobs/
levers (depending on
function) will lock when
power is applied. In the
event of power failure, the
opening will be unlocked.
EU, electrically unlocked
(fail secure):
Outside knob/lever or both
outside and inside knobs/
levers (depending on
function) will unlock when
power is applied. In the
event of power failure, the
opening will be locked.
Note: When mode is switched (from EL to EU or EU to EL) the lock requires a complete lock/unlock power cycle to synchronize to
the proper mode.
IMPORTANT! Connection of L-Series electrified mortise locks to a supply circuit containing electromagnetic devices (i.e., solenoid based) is not
recommended. If used, the resulting transient voltages could damage the lock. The transient voltage must be carefully suppressed at the equipment
producing it before connecting the lock to the same circuit. A varistor rated at 35 V (peak recurrent) may be used for transient voltage protection.
Troubleshooting
If lock does not operate.
Ensure the lock is powered with DC power. Do not use AC power.
Ensure the input voltage is between 10.8 and 26.4 volts DC.
L-Series Request-to-Exit (RX) Lock
RX utilizes a microswitch inside the lock case to detect rotation of the inside knob/lever. The switch then signals the use of the opening to the security system.
The RX is a removable module located on the bottom edge of the lock chassis. The module must be properly positioned to detect inside knob/lever
rotation. If not properly positioned, the lock and/or microswitch may be damaged.
Note: RX is not applicable with LM929X-Series locks.
RX module installation
1. The microswitch must be on the same side of the door as the
handing screw (facing the inside of the door).
2. Install the RX switch module as shown.
Change lock handing with RX
1. If the RX module is installed, remove the RX module.
2. Remove the handing screw.
3. Rotate the latch 180° (if necessary).
4. Reinstall the handing screw on the appropriate side.
5. Reinstall the RX module with the microswitch on the same side as
the handing screw.
Electrical rating:
3 A, 125 V AC; 2 A, 30 V DC
L-Series Electrified Locks
LM929X
L909X
Mode select
switch
(not furnished)
WARNINGS
Warnings indicate potentially hazardous conditions, which if not
avoided or corrected, may cause death or serious injury.
Lock to hinge/EPT
harness (not furnished)
Electrified hinge/
EPT (not furnished)
Install varistor
here if used
(not furnished)
12 or 24 V DC
Switch
L9091/93/95, L9493/95 and LM9291/93/95 functions lock both inside and
outside levers. Locking both levers will prevent normal egress from the
inside and will prevent the intended operation of an emergency exit.
WARNING
Electrical Requirements:
The L909X and LM929X-Series electrified locks
are powered by DC power only.
Do not use AC power.
• Voltage: 12 or 24 V DC (maximum 26.4 V,
minimum 10.8 V)
• Peak current: 0.4 amps
• Holding current: 0.010 amps
• Operating temperature: -22°F to 140°F
(-30°C to 60°C)
Maximum Total Wire Length
AWG
14
16
500'
300'
12 V
(152 m)
(91 m)
24 V
Up to 1000' 304 m
Note: Either lock wire may be attached to either power
supply terminal (+ or -).
Power supply
12 or 24 V DC
(not furnished)
WARNING
Handing screw
Microswitch
18
20
200'
100'
(61 m)
(30 m)
Blue (NO)
Yellow (NC)
Green
(common)
RX module
screws

Advertisement

loading

Summary of Contents for Schlage L Series

  • Page 1 L-Series Electrified Locks *P516-871* P516-871 L909X-Series Electrified Mortise Lock, WARNING LM929X-Series Electrified Two-Point Lock WARNINGS Warnings indicate potentially hazardous conditions, which if not Wiring Instructions and Specifications avoided or corrected, may cause death or serious injury. L-Series Electrified Lock All installations should be in accordance with local electrical codes and national electrical code, NFPA 70. L909X-Series and LM929X- Series electrified locks offer Electrical Requirements:...
  • Page 2 Deadbolt Monitor (DM) Deadbolt Monitor (DM) identifies the status of the deadbolt (extended or retracted). Normally open, normally closed, and common connections are provided. Note: Deadbolt monitor is only available on deadbolt models. Electrical rating: 3 A, 125 V AC; 2 A, 30 V DC. Latchbolt Monitor (LX) Latchbolt Monitor (LX) identifies the status of the latchbolt (extended or retracted).