Page 1
Installation manual Split system air conditioners RZQG71L9V1L RZQG71L8Y1L RZQG100L8Y1L RZQG125L8Y1L Installation manual English Split system air conditioners RZQG140L7Y1L...
Page 2
(mm) — ≥100 A, B, C — ≥100 ≥100 ≥100 B, E — ≥100 ≥1000 ≤500 A, B, C, E — ≥150 ≥150 ≥150 ≥1000 ≤500 — ≥500 D, E — ≥1000 ≤500 ≥500 — B, D ≥100 ≥500 B, D, E <H ≤½H ≥250...
4.5.2 Specifications of standard wiring components.... 4.5.3 To connect the electrical wiring on the outdoor unit..▪ The full set of latest technical data is available on the Daikin Finishing the outdoor unit installation ........Business Portal (authentication required). 4.6.1 To finish the outdoor unit installation ......
Fix the outdoor unit to the foundation bolts using nuts with resin washers (a). If the coating on the fastening area is stripped off, the metal can rust easily. Installation manual RZQG71L9V1L + RZQG71~125L8Y1L + RZQG140L7Y1L Split system air conditioners 4P473073-1A – 2019.04...
▪ Seal the insulation ends (sealant etc.) (e). ▪ Remove the piping intake plate (c) with screw (d). 2 Choose a piping route (a, b, c or d). RZQG71L9V1L + RZQG71~125L8Y1L + RZQG140L7Y1L Installation manual Split system air conditioners 4P473073-1A – 2019.04...
5 If you do NOT reach the target vacuum or CANNOT maintain the vacuum for 1 hour, do the following: ▪ Check for leaks again. ▪ Perform vacuum drying again. Installation manual RZQG71L9V1L + RZQG71~125L8Y1L + RZQG140L7Y1L Split system air conditioners 4P473073-1A – 2019.04...
2 Fix the label on the inside of the outdoor unit. There is a dedicated place for it on the wiring diagram label. RZQG71L9V1L + RZQG71~125L8Y1L + RZQG140L7Y1L Installation manual Split system air conditioners 4P473073-1A – 2019.04...
3 Fix the cables (power supply and interconnection cable) with a cable tie to the stop valve attachment plate and route the wiring according to the illustration above. Installation manual RZQG71L9V1L + RZQG71~125L8Y1L + RZQG140L7Y1L Split system air conditioners 4P473073-1A – 2019.04...
The indoor units are properly mounted. In case a wireless user interface is used: The indoor unit decoration panel with infrared receiver is installed. The outdoor unit is properly mounted. RZQG71L9V1L + RZQG71~125L8Y1L + RZQG140L7Y1L Installation manual Split system air conditioners 4P473073-1A – 2019.04...
Min Setpoints Differential Group Address Return Setting Press. Test Operation is displayed on the home menu. Cool Test Operation Return Setting Press within 10 seconds. Test run starts. Installation manual RZQG71L9V1L + RZQG71~125L8Y1L + RZQG140L7Y1L Split system air conditioners 4P473073-1A – 2019.04...
MUST comply with applicable legislation. Units MUST be treated at a specialised treatment facility for reuse, recycling and recovery. RZQG71L9V1L + RZQG71~125L8Y1L + RZQG140L7Y1L Installation manual Split system air conditioners 4P473073-1A – 2019.04...
7 Technical data Technical data A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is available on the Daikin Business Portal (authentication required). Service space: Outdoor unit Suction side In the illustrations below, the service space at the suction side is based on 35°C DB and cooling operation.
▪ K2R (A1P): Magnetic relay (E1H option) (RZQG_Y1) ▪ K2R (A2P): Magnetic relay White K10R, K13R~K15R Magnetic relay Yellow L1R~L3R Reactor Motor (compressor) Motor (upper fan) Motor (lower fan) RZQG71L9V1L + RZQG71~125L8Y1L + RZQG140L7Y1L Installation manual Split system air conditioners 4P473073-1A – 2019.04...
Page 16
4P473073-1 A 0000000. 4P473073-1A 2019.04...