Download Print this page

Technical Data - Siemens FT2080 Mounting & Installation

Fire terminal (touch)
Hide thumbs Also See for FT2080:

Advertisement

Technical data

6
6 Technical data
Supply input
Display
Interfaces
Ambient conditions
Mechanical data
Standards and approvals
14
FT2080 - Control and Indicating Terminal for use in fire detection and fire alarm systems installed in buildings.
2014/30/EU (EMC): EN 50130-4 / EN 61000-6-3 ; 2014/35/EU (LVD): EN 60950-1 ; 2011/65/EU (RoHS): EN 50581
The declared conformity can be seen in the EU Declaration of Conformity (DoC), which is obtainable via the Customer Support Center:
22 | 24
Building Technologies
Fire Safety
Voltage
Quiescent current (display illumination
dimmed 15%)
Maximum current (display illumination
100% and lamp test active)
Screen size
Resolution
2x slots for serial modules
2x slots for network modules
(SAFEDLINK)
1x Ethernet connection RJ45
1x connection for peripheral data bus
Operating temperature
Storage temperature
Moisture, condensation not permitted
Protection category (IEC60529)
Dimensions (W x H x D)
Weight without options
Color
VdS
FT2080-A1 / FT2080-C2
Tel. +49 89 9221-8000 or http://siemens.com/bt/download
DoC No.: CED-FT2080
DC 20...30 V
390 mA
700 mA
12"
1280 x 800 pixels
RS232 module for event printer
RS485 module for ESPA-4.4.4
interface, FAT, FBF, UGA or remote
EVAC-NL operation
Full functionality incl. degraded
mode function
Degraded mode function only
10/100 Mbit/s
X400
-8...+42 °C
-20...+60 °C
Max. 95 % rel.
IP30
427 x 200 x 25 mm
FT2080-A1: 2.544 kg
Foil: ∼RAL9010 Pure white,
∼RAL9006 White aluminum
G215024
Siemens Switzerland Ltd; Gubelstrasse 22
CH-6301 Zug
Technical data: see doc. 008836
A6V10462660_en--_b
2016-04-08

Advertisement

loading