INSTALLATION AND
MAINTENANCE INSTRUCTIONS
IDP-Zone-6
Six Zone Interface Module
BEFORE INSTALLING
If the modules will be installed in an existing operational
system, inform the operator and local authority that the
system will be temporarily out of service. Disconnect the
power to the control panel before installing the modules.
This system contains static sensitive components. Always
ground yourself with a proper wrist strap before handling
any circuits so that static charges are removed from the
body. The module housing should also be grounded.
NOTICE: This manual should be left with the owner/user
of this equipment.
GENERAL DESCRIPTION
The IDP-Zone-6 Six Zone Interface Module is intended
for use in an intelligent alarm system. Each module pro-
Compatible Two-wire System Sensor Smoke Detectors for use with IDP-Zone-6
DET.
MODEL
1151
1451
1451DH
2151
2451
2451TH
5451
1100
1400
** 2 100AT
2100B
2100D
2100S
2100TB
2100TD
2100TS
2300B
2300TB
2400
2400TH
* 2W-B
* 2W-TB
D H100LP
* Class B, Style B only
** No Accessory will be supported by 2100AT
K200-16-00
DETECTOR
DET. ID
MANUFACTURER
A
SYSTEM SENSOR
A
SYSTEM SENSOR
A
SYSTEM SENSOR
A
SYSTEM SENSOR
A
SYSTEM SENSOR
A
SYSTEM SENSOR
A
SYSTEM SENSOR
A
SYSTEM SENSOR
A
SYSTEM SENSOR
A
SYSTEM SENSOR
A
SYSTEM SENSOR
A
SYSTEM SENSOR
A
SYSTEM SENSOR
A
SYSTEM SENSOR
A
SYSTEM SENSOR
A
SYSTEM SENSOR
A
SYSTEM SENSOR
A
SYSTEM SENSOR
A
SYSTEM SENSOR
A
SYSTEM SENSOR
A
SYSTEM SENSOR
A
SYSTEM SENSOR
A
SYSTEM SENSOR
1
SPECIFICATIONS
Normal Operating Voltage:
Stand-By Current:
Alarm Current:
Temperature Range:
Humidity:
Dimensions:
Accessories:
Wire Gauge:
Max. IDC Wiring Resistance:
External Supply Voltage
DC Voltage:
Ripple Voltage:
Current:
IDC:
vides an interface between the intelligent alarm system
and a conventional alarm system loop. A common SLC
input is used for all modules, and the initiating device
loops share a common supervisory supply and ground.
Otherwise, each monitor operates independently from the
others. Each module has its own unique address.
A pair of rotary code switches is used to set the address
of the first module from 01 to 94. The remaining modules
are automatically assigned to the next five higher ad-
dresses. Provisions are included for disabling a maximum
of two unused modules to release the addresses to be
used elsewhere. Each module also has panel controlled
bicolor LED indicators. The panel can cause the LEDs to
blink, latch on, or latch off.
BASE MODEL
MAX DET.
B110LP, B401
B401, B401B
DH400
B110LP, B401
DH400, B401B, B401
B401, B401B
B401
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
15-32 VDC
2 mA
40 mA (assumes all six
LEDs solid on)
32ºF to 120ºF ( 0ºC to 49ºC)
10 to 93% Non-condensing
6.8˝ H x 5.8˝ W x 1.0˝ D
IDP-ACB Cabinet and chassis
12-18 AWG
25 ohms
18-28 volts power limited
0.1 volts RMS maximum
90mA per module
Supervised and power limited
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
I56-2733-003

Advertisement

loading

Summary of Contents for Honeywell SILEN KNIGHT IDP-Zone-6

  • Page 1 SPECIFICATIONS Normal Operating Voltage: 15-32 VDC Stand-By Current: 2 mA Alarm Current: 40 mA (assumes all six LEDs solid on) Temperature Range: 32ºF to 120ºF ( 0ºC to 49ºC) Humidity: 10 to 93% Non-condensing Dimensions: 6.8˝ H x 5.8˝ W x 1.0˝ D Accessories: IDP-ACB Cabinet and chassis INSTALLATION AND...
  • Page 2: Installation Steps

    INSTALLATION STEPS Included: (5) 1 x 4 Terminal Blocks (2) 1 ˝ Stand offs (3) Shunts 1. Cabinet Mounting In a clean, dry area, mount the backbox using the four holes provided in the back surface of the cabinet (Figure 2). (4) Machine Screws (1) Long Power Supply Jumper (2) Nuts...
  • Page 3: Wiring Notes

    The steps in Figures 4a and 4b describe and illustrate mod- 2. All wiring to the IDP-Zone-6 is done via terminal ule installation when the rear chassis position and the posi- blocks. In order to properly make electrical connec- tion in front of it will be filled. Front position installation tions strip approximately ˝...
  • Page 4 CONNECT MODULES TO LISTED COMPATIBLE BASE ADDRESS SILENT KNIGHT CONTROL 6 7 8 9 6 7 8 9 PANELS ONLY 3.9K EOL RESISTOR (INCLUDED) – – CLASS B IDC (TYPICAL) POWER TO THE NEXT INTERFACE MODULE MUST BE EXTERNALLY SWITCHED TO RESET THE DETECTORS. (+) AN FRM-1 RELAY CONTROL MODULE CAN BE USED TO SWITCH POWER FROM A (–) STANDARD POWER SUPPLY. SEE FIGUR 10. A/B SELECT STATUS A/B SELECT DISABLE 1 INDICATORS – DISABLE 2 FROM PANEL OR PREVIOUS DEVICE – TO NEXT DEVICE POWER-LIMITED SIGNAL LINE CIRCUIT (SLC) 32 VDC MAX. DETECTORS MUST BE UL LISTED COMPATIBLE WITH THE MODULE.
  • Page 5 SIGNAL LINE CIRCUIT (SLC) CONNECT MODULES 32 VDC MAX. TWISTED PAIR TO LISTED COMPATIBLE IS RECOMMENDED CONTROL PANELS ONLY. FROM PANEL OR TO NEXT DEVICE PREVIOUS DEVICE RELAY CONTROL MODULE POWER LIMITED DC POWER SUPPLY, LISTED FOR FIRE PROTECTION WITH BATTERY BACKUP ADDRESS LOOP C0248-01 Figure 7: Relay control module used to disconnect a power supply. EXTERNAL POWER SUPPLY — PCB 2 PCB 1 VIEW A-A...
  • Page 6: Fcc Statement

    7550 Meridian Circle Maple Grove, MN 55369-4927 763-493-6455; 800-328-0103 Fax: 763-493-6475 http://www.silentknight.com © 2006 Silent Knight 2/06 FCC Statement This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful in- terference, and (2) this device must accept any interference received, including interference that may cause undesired operation.