Siemens SIMATIC S7-1500 Manual page 52

Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Technical specifications
Switching capacity of outputs
With resistive load, max.
With lamp load, max.
Load resistance range
Low limit
High limit
Output voltage
For "1" signal, min.
Output current
For "1" signal, rated value
For "0" signal, residual current, max.
Switching frequency
With resistive load, max.
With inductive load, max.
With lamp load, max.
Total current of outputs
Max. current per channel
Total current of the outputs (per module)
Horizontal mounting position
Vertical mounting position
Cable length
shielded, max.
unshielded, max.
Interrupts/diagnostics/status information
Fail-safe values can be switched to
Interrupts
Diagnostic interrupt
Diagnostic alarms
Diagnostics
Monitoring of supply voltage
Wire break
Short-circuit
Group error
Diagnostics display LED
RUN LED
ERROR LED
Monitoring of the supply voltage (PWR-LED)
Channel status display
For channel diagnostics
For module diagnostics
52
Up to 40 ℃, max.
Up to 60 ℃, max.
Up to 40 ℃, max.
2 A
10 W
12 Ω
2000 Ω
24 V; L+ (-0.5 V)
2 A
0.5 mA; PP switching or separate P and
M-switch, PM-switching: max. 1 mA
30 Hz
0.1 Hz
10 Hz
2 A
16 A
8 A
8 A
1000 m
500 m
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes; green LED
Yes; red LED
Yes
Yes; green LED
Yes; red LED
Yes; red LED
Digital output module F-DQ 8x24VDC/2A PPM (6ES7526-2BF00-0AB0)
6ES7526-2BF00-0AB0
Manual, 01/2016, A5E03858037-AA

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic et 200 mp

Table of Contents