Design And Principle Of Operation; Typetesting - Samson STM 5343 Mounting And Operating Instructions

Safety temperature monitor, temperature regulator, safety temperature limiter, double thermostat
Table of Contents

Advertisement

Design and principle of operation

2
Design
operation
Safety temperature monitors (STM)
The snap-action switch is triggered if the
temperature at the bulb rises above the ad-
justed set point. When the temperature falls
below the set point by approximately 8 K,
the switch returns to its original position.
The electric circuit is opened when the tem-
perature at the bulb falls below –20 °C. The
circuit is automatically closed again when
the temperature at the bulb rises above
–20 °C.
The circuit remains permanently open if the
measuring system is broken.
Temperature regulators (TR)
The snap-action switch is triggered if the
temperature at the bulb rises above the ad-
justed set point. When the temperature falls
below the set point by approximately 4 K,
the switch returns to its original position.
Safety temperature limiters (STL)
The snap-action switch is triggered and
locked if the temperature at the bulb rises
above the adjusted set point. When the tem-
perature falls below the set point by approx-
imately 10 %, the snap-action switch can be
unlocked manually.
The electric circuit is opened when the tem-
perature at the bulb falls below –20 °C. The
circuit is automatically closed again when
the temperature at the bulb rises above
–20 °C.
4
EB 5206 EN
and
principle
The circuit remains permanently open if the
of
measuring system is broken. It is not possi-
ble to unlock the device.
2.1

Typetesting

The thermostats are typetested by the Ger-
man Technical Inspectorate (TÜV) according
to DIN EN 14597.
Type
5343
5344
5345
DIN register number
STW120908
TR120808
STB120708