Section 6. Refrigerant Line Routing - Lennox LIAC024-180P431 Installation Manual

Table of Contents

Advertisement

5.4 Reuse Existing Refrigerant Lines
If using existing refrigerant lines make certain that
all joints are brazed, not soldered.
For retrofit applications, where the existing refrigerant
lines will be used, the following precautions should
be taken:
Ensure that the refrigerant lines are the correct
size. Refer to Section 2.2 listed and Table 5.1.
Ensure that the refrigerant lines are free of leaks,
acid, and oil.
Note: The manufacturer recommends installing only
approved matched indoor and outdoor systems. All
of the manufacturer's split systems are A.H.R.I. rated
only with TXV indoor systems. Some of the benefits
of installing approved matched indoor and outdoor
split systems are maximum efficiency, optimum per -
formance and the best overall system reliability.

Section 6. Refrigerant Line Routing

6.1 Precautions
Important: Take precautions to prevent noise within
the building structure due to vibration transmission
from the refrigerant lines.
For Example:
When the refrigerant lines have to be fastened to floor joists or other framing in a structure, use isolation type
hangers.
Isolation hangers should also be used when refrigerant lines are run in stud spaces or enclosed ceilings.
Where the refrigerant lines run through a wall or sill, they should be insulated and isolated.
Isolate the lines from all ductwork.
Minimize the number of 90º turns.
Side View
8 Feet Maximum
Secure Suction line from joists using isolators every 8 ft. Secure
Liquid Line directly to Suction line using tape, wire, or other
appropriate method every 8 ft.
Isolation From Joist/Rafter
Comply with National, State, and Local Codes when
isolating line sets from joists, rafters, walls, or other
structural elements.
8 Feet Maximum
7
Joist/Rafter
Isolator
Line Set

Advertisement

Table of Contents
loading

This manual is also suitable for:

Liac048-180p431Liac036-180p431Liac060-180p431

Table of Contents