Basic segment display
Step
At initial power input
While setting communication
between indoor and outdoor unit
(Addressing)
After communication setting
(usual occasion)
❇ I/U : Indoor unit
❇
Setting outdoor unit option switch and key function
Setting outdoor unit option switches : A TYPE
❇ If you install HR products, you must match the address between the MCU and the indoor unit .
❇
Switch
Setting
SW51 /
SW52
On
K6
Off
K7
K8
SW53
On
On
On
Off
Off
On
Off
Off
SW57
DVM S HE_IM_DB68-05461A-08_EN.indd 95
Display content
Checking segment display
Number of connected indoor
units
Transmit/Reception address
Function
Setting total number of installed indoor unit
SW51: Tens digit, SW52: Units digit
Enable maximum capacity restriction for cooling
operation
Disable maximum capacity restriction for
cooling operation
Outdoor unit address: No . 1
Outdoor unit address: No . 2
Outdoor unit address: No . 3
Outdoor unit address: No . 4
Setting total number of connected MCU
SEG 1
SEG 2
"8"
"8"
SEG 1
SEG 2
"A"
"d"
SEG 1
SEG 2
I/U: "A"
I/U: "0"
MCU: "C"
MCU: "1"
Setting can be done from the main outdoor unit
only (sub unit: setting is unnecessary)
Ex) When 12 indoor units are installed
SW51: 1, SW52: 2
Restrict excessive capacity increase when
operating indoor units with small capacity
Selecting outdoor unit address
Main unit
Sub unit 1
Sub unit 2
Sub unit 3
Setting can be done from Main unit only .
Ex) When 3 MCUs are installed SW57:3, When
10 MCUs are installed SW57:A
Display
SEG 3
SEG 4
"8"
"8"
SEG 3
SEG 4
Number of
communicated units
❋ Refer to "View Mode"
for communication
address
SEG 3
SEG 4
Reception address (in
decimal number)
Remarks
-
95
2017-03-24 오후 1:38:44