Chapter 5 : Front Panel - Delta Electronics STS30002SR10135 User Manual

Infrasuite power management. static transfer switch
Table of Contents

Advertisement

No.
Item
S1 LED
1
S2 LED
2
S1_ON
3
LED
S2_ON
4
LED
O/P
5
LED
Test
6
Button

Chapter 5 : Front Panel

8
7
1
3
S1
S1-ON
O/P
TEST
S2
S2-ON
6
2
4
Green. The LED indicates the condition of input source
1. If the input source 1 is within the acceptable range, the
LED will light up as green. If the input source 1 is out of the
acceptable range, the LED will be off.
Green. The LED indicates the condition of input source
2. If the input source 2 is within the acceptable range, the
LED will light up as green. If the input source 2 is out of the
acceptable range, the LED will be off.
Green. If the STS uses input source 1 to supply power to the
output, the LED will light up as green. If not, the LED will be
off.
Green. If the STS uses input source 2 to supply power to the
output, the LED will light up as green. If not, the LED will be
off.
Green. The LED indicates the output condition (voltage is >
60Vac). If there is output, the LED will light up as green. If
not, the LED will be off.
Use the button to test the STS. Press the button once and
the STS will transfer to the 2
transfer back to the original preferred source.
1
NETWORK
5
4
Description
nd
source for 1 minute and then
1 3
Chapter 5
Front Panel
2
3
LOCAL