SCROLL COMPRESSOR

DISCHARGE
SUCTION
Early Model HS26
Compressor shown
FIGURE 1
I−APPLICATION
All major components (indoor blower and coil) must be
matched according to Lennox recommendations for the
compressor to be covered under warranty. Refer to the
Engineering Handbook for approved system matchups. A
misapplied system will cause erratic operation and can re
sult in early compressor failure.
II−SCROLL COMPRESSOR
The scroll compressor design is simple, efficient and re
quires few moving parts. A cutaway diagram of the scroll
compressor is shown in figure 1.The scrolls are located in
the top of the compressor can and the motor is located just
below. The oil level is immediately below the motor.
The scroll is a simple compression concept centered
around the unique spiral shape of the scroll and its inherent
properties. Figure 2 shows the basic scroll form. Two iden
tical scrolls are mated together forming concentric spiral
shapes (figure 3 ). One scroll remains stationary, while the
other is allowed to orbit" (figure 4). Note that the orbiting
scroll does not rotate or turn but merely orbits" the station
ary scroll.
SCROLL FORM
CROSS−SECTION OF SCROLLS
DISCHARGE
DISCHARGE
PRESSURE
TIPS SEALED BY
DISCHARGE PRESSURE
The counterclockwise orbiting scroll draws gas into the out
er crescent shaped gas pocket created by the two scrolls
(figure 4 − 1). The centrifugal action of the orbiting scroll
seals off the flanks of the scrolls (figure 4 − 2). As the orbiting
motion continues, the gas is forced toward the center of the
scroll and the gas pocket becomes compressed (figure 4
−3). When the compressed gas reaches the center, it is dis
charged vertically into a chamber and discharge port in the
top of the compressor (figure1). The discharge pressure
forcing down on the top scroll helps seal off the upper and
lower edges (tips) of the scrolls (figure 3 ). During a single
orbit, several pockets of gas are compressed simultaneous
ly providing smooth continuous compression.
The scroll compressor is tolerant to the effects of liquid re
turn. If liquid enters the scrolls, the orbiting scroll is allowed
to separate from the stationary scroll. The liquid is worked
toward the center of the scroll and is discharged. If the
compressor is replaced, conventional Lennox cleanup
practices must be used.
Due to its efficiency, the scroll compressor is capable of
drawing a much deeper vacuum than reciprocating com
pressors. Deep vacuum operation can cause internal fu
site arcing resulting in damaged internal parts and will re
sult in compressor failure. Never use a scroll compressor
for evacuating or pumping−down" the system. This type of
damage can be detected and will result in denial of warran
ty claims.
NOTE − During operation, the head of a scroll compressor
may be hot since it is in constant contact with discharge
gas.