Interface Overview; User Interface; Keypad - Carrier WeatherMaker 48TC Series Installation Instructions Manual

Single package rooftop with gas heat/electric cooling vertical air flow unit with puron (r-410a) refrigerant
Hide thumbs Also See for WeatherMaker 48TC Series:
Table of Contents

Advertisement

Table 9 — Economizer Module - Right Hand Terminal
LABEL
TYPE
Top Right Terminal Blocks
AUX2 I
24 vac IN
The first terminal is not used.
Shut Down (SD) or HEAT (W)
Conventional only
OCC
24 vac IN
and
Heat Pump Changeover (O-B) in Heat
Pump mode.
E-GND
E-GND
Occupied/Unoccupied Input
EXH1
24 vac OUT Exhaust Fan 1 Output
Programmable:
Exhaust fan 2 output
or
AUX1 O
24 vac OUT
ERV
or
System alarm output
Bottom Right Terminal Blocks
Y2 in - Cooling Stage 2 Input from space
Y2-I
24 vac IN
thermostat
Y2 out - Cooling Stage 2 Output to stage
Y2-O
24 vac OUT
2 mechanical cooling
Y1 in - Cooling Stage 2 Input from space
Y1-I
24 vac IN
thermostat
Y1 out - Cooling Stage 2 Output to stage
Y1-O
24 vac OUT
2 mechanical cooling
C
COM
24 vac Common
R
24 vac
24 vac Power (hot)
S-BUS
TERMINALS
(1 AND 2)
Fig. 48 — S-Bus Sensor DIP Switches
Use Fig. 48 and Table 10 to locate the wiring terminals for each
enthalpy control sensor.
Blocks
DESCRIPTION
DIP
SWITCH
LABEL
DIP
SWITCHES
(3)
S-BUS
2 PIN SIDE
CONNECTOR
Table 10 — HH57AC081 Sensor Wiring Terminations
TERMINAL
NUMBER
LABEL
1
S-BUS
2
S-BUS
Use Fig. 48 and Table 11 to set the DIP switches for the desired
use of the sensor.
Table 11 — HH57AC081 Sensor DIP Switch
DIP SWITCH POSITIONS FOR SWITCHES 1, 2, AND 3
USE
1
DA
OFF
RA
ON
OA
OFF
NOTE: When a S-bus sensor is connected to an existing network,
it will take 60 minutes for the network to recognize and auto-con-
figure itself to use the new sensor.
During the 60 minute setup period, no alarms for sensor failures
(except SAT) will be issued and no economizing function will be
available.
CO
SENSOR WIRING
2
When using a CO
sensor, the black and brown common wires are
2
internally connected and only one is connected to "IAQ COM" on
the W7220. Use the power from the W7220 to power the CO
sensor OR make sure the ground for the power supplies are com-
mon. See Fig. 49 for CO
CO
SENSOR
2
24V
ANALOG
OUT
1
POWER SUPPLY. PROVIDE DISCONNECT
MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
Fig. 49 — CO

INTERFACE OVERVIEW

This section describes how to use the economizer's user interface
for:
Keypad and menu navigation
Settings and parameter changes
Menu structure and selection

USER INTERFACE

The user interface consists of a 2-line LCD display and a 4-button
keypad on the front of the economizer controller.

KEYPAD

The four navigation buttons (see Fig. 50) are used to scroll
through the menus and menu items, select menu items, and to
change parameter and configuration settings.
35
TYPE
DESCRIPTION
S-BUS
Communications
S-BUS
(Enthalpy Control
Sensor Bus)
S-BUS
Communications
S-BUS
(Enthalpy Control
Sensor Bus)
2
ON
OFF
OFF
sensor wiring.
2
RED
L1
(HOT)
BLACK
L2
1
YELLOW
+
BROWN
ORANGE
GREEN
Sensor Wiring
2
3
OFF
OFF
OFF