INSTALLATION
OUTDOOR TEMPERATURE SENSOR (INCLUDED)
Outdoor temperature can be measured by installing an 8052 sensor to the ODT terminals and enabling the outdoor
sensor in the installer setup menu . When an outdoor sensor is installed, the features below will be enabled .
In heat pump mode the outdoor temperature sensor can be used to efficiently utilize an air source heat pump:
• When the outdoor temperature is less than the Low Balance Point, the heat pump will be locked out and only
auxiliary heating will be used to provide heating .
• When the outdoor temperature is higher than the High Balance Point, the auxiliary heating will be locked out and
only the heat pump will be used to provide heating .
Indoor Air Quality functions can use the outdoor temperature sensor to:
• Control humidification setpoint based on outdoor temperature to prevent condensation
• Lock out humidification for temperatures over 60°F or below -30°F .
• Lock out ventilation based on high and/or low outdoor temperatures .
• Display outdoor temperature on thermostat .
Outdoor temperature sensor should
be mounted:
• On side of building out of direct sunlight
(north side recommended) .
• Above snow line .
• At least 3' away from exhaust vents and
condensing lines .
• Using less than 300' of wire .
• Do not route wires along 120 VAC lines .
OPTIONAL WIRELESS OUTDOOR TEMPERATURE AND HUMIDITY SENSOR
For installations where it is difficult to wire the included 8052 outdoor temperature sensor, a Model 8056 wireless
outdoor sensor can be used . The Model 8056 module has two radio units, one that is placed on the equipment control
module as shown below, and a second radio that is placed outside . See the Model 8056 Installation Instructions for
detailed directions regarding installation .
6
Outdoor Sensor
INSTALLATION
RETURN AIR TEMPERATURE SENSOR (OPTIONAL)
Return air temperature can be measured by attaching an 8052 sensor to the RAT terminals . The return sensor must
be enabled in the installer setup menu . The return air temperature sensor provides protection in the event that the
equipment control module loses connection with the thermostat . In the event that the thermostat connection is lost,
the equipment control module will use the return air temperature sensor to maintain a temperature greater than 40°F
and less than 100°F .
1 . Locate the Aprilaire Model 8052 sensor
in the return trunk .
2 . Mount the sensor according to the
installation instructions provided with
the sensor .
3 . Wire the sensor to the equipment
control module RAT terminals .
LEAVING AIR TEMPERATURE SENSOR (OPTIONAL)
Leaving air temperature can be measured by attaching an 8052 sensor to the LAT terminals . The leaving air
temperature sensor measurement is displayed during the installer test for diagnostic purposes .
IMPORTANT
Do not mount the sensor in direct line-of-sight of the heat exchanger, cooling coils, or UV lights as this may cause
the sensor to report false temperature readings .
1 . Locate the Aprilaire Model 8052 sensor in the supply trunk, after the heat exchanger and cooling coils . (See
shaded areas in figure below .)
2 . Mount the sensor according to the installation instructions provided with the sensor .
3 . Wire the sensor to the equipment control module LAT terminals .
LOCATE
SENSOR
IN SHADED
AREA .
7