Bryant Preferred Series Installation Instructions Manual page 31

Single package rooftop gas heating/electric cooling unit with puron (r-410a) refrigerant
Hide thumbs Also See for Preferred Series:
Table of Contents

Advertisement

MENU
PARAMETER
ACT COUNT
ACTUATOR
EXH1 OUT
STATUS
EXH2 OUT
(cont)
ERV
MECH COOL ON
or
HEAT STAGES ON
FAN SPEED
W (HEAT IN)
MAT SET
LOW T LOCK
DRYBLB SET
ENTH CURVE
DCV SET
SETPOINTS
MIN POS
VENTMAX
VENTMIN
Table 11 — W7220 Menu Structure* (cont)
PARAMETER
PARAMETER
DEFAULT
RANGE AND
VALUE
INCREMENT
N/A
1 to 65,535
OK/Alarm (on
N/A
Alarm menu)
OFF
ON/OFF
OFF
ON/OFF
OFF
ON/OFF
0
0, 1, or 2
N/A
LOW or HIGH
N/A
ON/OFF
38°F to 70°F
(3°C to 21°C);
53°F (12°C)
increment by 1
degree
–45°F to 80°F
(–43°C to 27°C);
32°F (0°C)
increment by 1
degree
48°F to 80°F
(9°C to 27°C);
63°F (17°C)
increment by
1 degree
ES1,ES2,ES3,ES4,
ES3
or ES5
500 to 2000 ppm;
1100ppm
increment by 100
2.8 V
2 to 10 vdc
2 to 10 vdc
2.8 V
100 to 9990 cfm;
increment by 10
2 to 10 vdc
2 to 10 vdc or 100
to 9990 cfm
increment by 10
2.25 V
100 to 9990 cfm;
increment by 10
2 to 10 vdc
31
EXPANDED PARAMETER NAME
Displays number of times actuator has cycled.
1 cycle equals 180 degrees of actuator movement in any
direction.
Displays ERROR if voltage or torque is below actuator range.
EXHAUST STAGE 1 RELAY OUTPUT
Displays ON when damper position reaches programmed
percentage set point.
Output of EXH1 terminal:
ON = relay closed
OFF = relay open
EXHAUST STAGE 2 RELAY OUTPUT
Output of AUX1 O terminal
Displays ON when damper position reaches programmed
percentage set point.
ON = 24 vac output
OFF = No output
Displays only if AUX1 O = EXH2
ENERGY RECOVERY VENTILATOR
Output of AUX1 O terminal; displays only if AUX1 O = ERV
ON = 24 vac output
OFF = No Output
Displays stage of mechanical cooling that is active.
Displays the stage of heat pump heating that is active.
SUPPLY FAN SPEED
Displays speed setting of fan on a 2-speed fan unit.
HEAT DEMAND STATUS
Displays status of heat demand on a 2-speed fan unit.
SUPPLY AIR SETPOINT
The economizer will modulate the OA damper to maintain the
mixed air temperature at the set point
COMPRESSOR LOW TEMPERATURE LOCKOUT
Set point determines outdoor temperature when the mechanical
cooling cannot be turned on. Commonly referred to as the
Compressor lockout. At or below the set point, the Y1-O and Y2-
O will not be energized on the controller.
OA DRY BULB TEMPERATURE CHANGEOVER SETPOINT
Dry bulb set point will only appear if using dry bulb changeover.
Set point determines where the economizer will assume outdoor
air temperature is good for free cooling; e.g.; at 63°F unit will
economize at 62°F and below and not economize at 64°F and
above. There is a 2°F deadband.
ENTHALPY CHANGEOVER CURVE
ES curve will only appear if using enthalpy changeover.
Enthalpy boundary "curves" for economizing using single
enthalpy. See page 37 for description of enthalpy curves.
DEMAND CONTROLLED VENTILATION
Displays only if CO
sensor is connected. Set point for Demand
2
Controlled Ventilation of space. Above the set point, the OA
dampers will modulate open to bring in additional OA to maintain
a space ppm level below the set point.
VENTILATION MINIMUM POSITION
Displays ONLY if a CO
sensor is NOT connected.
2
DCV MAXIMUM DAMPER POSITION
Displays only if a CO
sensor is connected.
2
Used for Vbz (ventilation max cfm) set point. VENTMAX is the
same setting as MIN POS would be if unit did not have CO
sensor.
If OA, MA, RA, and CO
sensors are connected and DCV CAL
2
ENABLE is set to AUTO mode, the OA dampers are controlled
by CFM and displays from 100 to 9990 CFM.
With 2-speed fan units, VENTMAX L (low speed fan) and
VENTMAX H (high speed fan) settings are required. Default for
VENTMAX L is 3.2V and VENTMAX H is 2.8V
DCV MINIMUM DAMPER POSITION
Displays only if a CO
sensor is connected. Used for Va
2
(ventilation min cfm) set point. This is the ventilation for less than
maximum occupancy of the space.
If OA, MA, RA, and CO
sensors are connected and DCV CAL
2
ENABLE is set to AUTO mode, the OA dampers are controlled
by CFM and displays from 100 to 9990 CFM.
With 2-speed fan units VENTMIN L (low speed fan) and
VENTMIN H (high speed fan) settings are required. Default for
VENTMIN L is 2.5V and VENTMIN H is 2.25V