7.5.2

Preparing cables

To connect a cable, follow these steps:
Step
Step
num
ber:
1
Remove cable sheath
and shielding
2
Stripping cables
3
Additional preparation Compact the wires or use wire end ferrules.
4
Wiring the connectors
7.5.3

Connecting the cable using push-in terminals

Note
Cable cross-sections
With small conductor cross-sections and stranded cables, there is a risk that the cable will be
bent when it is plugged into the terminal.
Recommendation
Use wire end ferrules to prevent contact problems or short circuits.
You can find information on preparing the cables in section "Preparing cables (Page 63)".
Connecting the cable
Procedure
1. Prepare the cables.
2. In case of a stranded wire:
Press the screwdriver against the spring release.
The spring bracket opens.
3. Insert the wire into the round opening as far as it will go.
4. In case of a stranded wire:
Remove the screwdriver from the spring release.
SIMATIC CFU
Commissioning Manual, 08/2019, A5E39252870-AD
7.5 Connect cables for sensors, actuators and power supply to the connector
Cable (you can find additional information in section "Cable cross-sections and ferrules
Flexible (stranded), without wire end ferrule, un‐
prepared
● Length 60 mm
● SIMATIC CFU PA Bundle with aluminum housing:
Also remove the sheath of the PA bus cables in the area of the shield terminals:
Bottom terminals: Remove the sheath in the area between 150 mm to 165 mm
Top terminals: Remove the sheath in the area between 140 mm to 155 mm
● Stripping cable for connectors with screw-type terminals: 7 mm
● Stripping cable for connectors with push-in terminals: 10 mm
Observe the following table.
Connect the cables to the plug.
● Connecting the cable using push-in terminals (Page 63)
● Connecting cables using screw terminals (Page 64)
(Page 186)")
Solid without wire end ferrule, flexible
(stranded) with wire end ferrule or ultra‐
sonically sealed
None
Connecting
63