Dimensions:
Weight:
OPERATING RANGE
ANALOGUE OUTPUT
CONTROLS
AMBIENT TEMPERATURE RANGE
Operating:
Accuracy:
Storage:
9. SPECIFICATION
115mm x 130mm x 88mm.
1.2kg.
0 to 50ppm H
4 - 20mA two wire. The 'sensing resistor'
can be either connected between the fuse
supply and the sensor (sinking current) or
connected between the sensor and 0V
(sourcing current). 4 - 20mA represents
0 - 50ppm H
Zero and span potentiometers accessible
through label plate.
-40°C to +55°C.
Operation at temperatures above +50°C
or below -20°C for prolonged periods can
reduce operating life of the cell.
Baseline change (-10°C to +45°C) less
than ±3ppm H
Span change (-10°C to +45°C) ±10 ppm
H
S.
2
-0°C to +25°C (recommended).
26
S
2
S.
2
S.
2