Delta Amplon RT Series User Manual page 54

Single phase 5/6/8/10 kva
Hide thumbs Also See for Amplon RT Series:
Table of Contents

Advertisement

Setup Item
Auto Restart
Auto Start on AC
NOTE :
In Setting Menu, the sub item Option 1 under the item Energy Saving
cannot be changed.
Battery
z
z
Setup Item
Automatic Battery Test
Deep Discharge Test
Low Battery
Warning Capacity
Warning of
Remaining Time
Runtime Limitation
Charge Mode
Float Charging
Voltage
Internal Charging
Current
External Battery Type *
Amplon RT Series
Selectable Value
Enable/ Disable
Enable/ Disable
Selectable Value
No test/ Daily/ Weekly/
Biweekly/ Monthly
20-90% (per step: 10%)
0-95%
(per step: 5%)
0-60mins
(per step: 1min)
Disable/ 1/ 2/ 3..../ 240mins
(per step: 1min)
2-stage/ 3-stage
Auto/ Customize
(2.20 - 2.35 V/ cell,
per step: 0.01V)
For 5K/ 6K: 1/ 2/ 3/ 4/ 5/ 6/ 7/ 8A*
For 8K/ 10K: 1.5/ 2/ 3/ 4/ 5/ 6A
Standard battery pack/
3
Customer own batt. pack
5 0
Default Value
Enable
Disable
Default Value
No test
90%
10%
2mins
Disable
2-stage
Auto
1
2
1A (5K/ 6K)*
1.5A (8K/ 10K)*
2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Amplon rt-8kAmplon rt-5kAmplon rt-6kAmplon rt-10k

Table of Contents