1. SPECIFICATIONS

Model SRR25ZM-S
Item
Power source
Nominal cooling capacity (range)
Nominal heating capacity (range)
Power consumption
Max power consumption
Running current
Inrush current, max current
Power factor
Operation data
EER
COP
Sound power level
Sound pressure level ①
Sound pressure level ②
Sound pressure level ③
Silent mode sound pressure level
Exterior dimensions (Height x Width x Depth)
Exterior appearance ( Munsell color )
Net weight
Compressor type & Q'ty
Compressor motor (Starting method)
Refrigerant oil (Amount, type)
Refrigerant (Type, amount, pre-charge length)
Heat exchanger
Refrigerant control
Fan type & Q'ty
Fan motor (Starting method)
Air flow
Available external static pressure
Outside air intake
Air filter, Quality / Quantity
Shock & vibration absorber
Electric heater
Remote control
Operation
Room temperature control
control
Operation display
Safety equipments
Refrigerant piping size (O.D)
Connecting method
Attached length of piping
Installation
Insulation for piping
data
Refrigerant line (one way) length
Vertical height diff. between O.U. and I.U.
Drain hose
Drain pump, max lift height
Recommended breaker size
L.R.A. (Locked rotor ampere)
Interconnecting wires
IP number
Standard accessories
Option parts
Note (1) The data are measured at the following conditions.
Item
Indoor air temperature Outdoor air temperature
Operation
DB
Cooling
27˚C
Heating
20˚C
(2) This air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound level indicates the value in an anechoic chamber. During operation these
values are somewhat higher due to ambient conditions.
(4) Select the breaker size according to the own national standard.
Model
kW
kW
Cooling
Heating
kW
Cooling
Heating
A
Cooling
%
Heating
Cooling
Heating
Cooling
Heating
Cooling
dB(A)
Heating
Cooling
Heating
mm
kg
kW
kg
W
Cooling
3
m
/min
Heating
Hi: 10.0 Me: 9.0 Lo: 8.0 ULo: 6.0
Pa
35 (Initial static pressure with air filter:5Pa)
Compressor overheat protection, Overcurrent protection, Drain error protection,
Frost protection, Serial signal error protection, Indoor fan motor error protection,
Heating overload protection( High pressure control ), Cooling overload protection
mm
m
m
m
mm
A
A
Size x Core number
WB
DB
WB
19˚C
35˚C
24˚C
7˚C
6˚C
Indoor unit SRR25ZM-S
1 Phase, 220 - 240V, 50Hz
2.5 ( 1.0 (Min.) - 3.3 (Max.))
3.4 ( 1.4 (Min.) - 4.8 (Max.))
0.570 ( 0.21 - 0.86 )
0.750 ( 0.26 - 1.32 )
3.0 / 2.9 / 2.8 (220/ 230/ 240 V)
3.9 / 3.7 / 3.6 (220/ 230/ 240 V)
3.9 / 3.7 / 3.6 (220/ 230/ 240 V), MAX 8
56
59
Hi: 37 Me: 33 Lo: 30 ULo: 24
Hi: 40 Me: 37 Lo: 34 ULo: 28
Hi: 31 Me: 28 Lo: 26 ULo: 21
Hi: 33 Me: 30 Lo: 28 ULo: 23
Hi: 39 Me: 35 Lo: 32 ULo: 25
Hi: 44 Me: 41 Lo: 38 ULo: 31
200 x 750 x 500
20.5
R410A 1.2 in outdoor unit (incl. the amount for the piping of 15m )
Louver fins & inner grooved tubing
Capillary tubes + Electronic expansion valve
Centrifugal fan x 2
51 x1 (Direct drive)
Hi: 9.5 Me: 8.0 Lo: 6.5 ULo: 4.5
Not possible
Polypropylene net x 1
Cushion rubber (for fan motor)
Wireless remote control
Microcomputer thermostat
RUN: Green, TIMER: Yellow, HI POWER: Green, ECONO: Green
Liquid line: φ6.35 ( 1/4" )
Flare connection
Necessary (Both sides), independent
Max. 10 (Outdoor unit is higher) / Max. 10 (Outdoor unit is lower)
Hose connectable ( VP 25 )
Built-in, MAX600
3.1 / 2.9 / 2.8 (220/ 230/ 240 V)
2
1.5mm
x 4 cores (Including earth cable) / Terminal block (Screw fixing type)
IPX0
Mounting kit, Joint for drain piping
Wired remote control, Interface kit ( SC-BIKN-E ), Bottom air inlet kit
The pipe length is 5m.
(5) Mike positions of measureing sound pressure
Standards
Note
Non-duct
ISO5151-T1
(with air fillter)

-
-
'15 • SR-T-185
SRR25ZM-S
Outdoor unit SRC25ZMX-S
1.65
85
88
4.39
4.53
60
60
47
47
47
47
47
47
Cooling:41 / Heating:42
595 x 780(+62) x 290
Stucco white
( 4.2Y 7.5/1.1 ) near equivalent
35
RM-B5077MDE1( Rotary type ) x 1
0.75 ( Inverter driven )
0.35 ( DIAMOND FREEZE MA68 )
M fins & inner grooved tubing
Propeller fan x 1
24 x1 (Direct drive)
29.5
27.0
0
Rubber sleeve (for fan motor & compressor)
Gas line: φ9.52 ( 3/8" )
Flare connection
Max. 15
Holes φ20 x 2 pcs
16
IPX4
level of indoor unit is shown below.
RWA000Z263
External static
pressure
for ②, ③
: 10Pa