Carrier 50TCM Series Installation, Operation And Maintenance Manual page 9

Package rooftop units - 50hz, nominal cooling capacity 6 - 12.5 tons, hfc r-410a refrigerant
Table of Contents

Advertisement

48--- in (1219 mm)
Unit disconnect is mounted on panel
36--- in (914 mm)
If dimension--- B is 12--- in (305 mm)
A
18--- in (457 mm)
No disconnect, convenience outlet option
18--- in (457 mm)
Recommended service clearance (use electric screwdriver)
12--- in (305 mm)
Minimum clearance (use manual ratchet screwdriver)
B
12--- in (305 mm)
If dimension--- A is 36--- in (914 mm)
Special
Check for sources of flue products within 10--- ft of unit fresh air intake hood
36--- in (914 mm)
Side condensate drain is used
C
18--- in (457 mm)
Minimum clearance
42--- in (1067 mm)
Surface behind servicer is grounded (e.g., metal, masonry wall, another unit)
D
36--- in (914 mm)
Surface behind servicer is electrically non--- conductive (e.g., wood, fiberglass)
C
B
Page 9
(cont.)
D
A